Worked example
Example: G 100 1/s at 10 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mixing given as | Velocity gradient G |
| Velocity gradient | 100.00 1/s |
| Power input to the water | 0.54600 kW |
| Tank volume | 65.100 m³ |
| Kinematic viscosity | 1.3100e-06 m²/s |
| Density | 999.70 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Velocity gradient | 100.00 1/s |
| Energy dissipation rate per unit mass | 0.013100 J/kg |
| Kolmogorov microscale | 114.46 µm |
Open this example in the calculator and change any input.
Formula
\(\varepsilon = \frac{P}{\rho V} = G^2\nu, \quad \eta_K = \left(\frac{\nu^3}{\varepsilon}\right)^{1/4} = \left(\frac{\nu}{G}\right)^{1/2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{input}\) | Mixing given as | - |
| \(G\) | Velocity gradient | 1/s |
| \(P\) | Power input to the water | W |
| \(V\) | Tank volume | m³ |
| \(\nu\) | Kinematic viscosity | m²/s |
| \(\rho\) | Density | kg/m³ |
| \(\varepsilon\) | Energy dissipation rate per unit mass | J/kg |
| \(\eta_K\) | Kolmogorov microscale | m |
Method and standards
Kolmogorov scaling of turbulence.
Where it is used
- Rapid mix and flocculator design.
- Relating floc size limits to mixing.
Common mistakes
- Using dynamic viscosity in place of kinematic.
- Assuming the average ε holds near the impeller.
Assumptions and limits
- Isotropic turbulence, uniform dissipation.
Questions and answers
Why does it matter for flocculation?
Flocs smaller than the microscale see laminar shear; those larger are torn by eddies, which limits floc size at high G.
How does it change with G?
η = (ν/G)^½, so a hundredfold rise in G shrinks the smallest eddies tenfold.
What do the defaults represent?
An illustrative case: G 100 1/s at 10 C. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 6-10, eqs. 6-136 to 6-140 and Example 6-10