Worked example
Example: Hot well 50 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Liquid | Water (vapour pressure from IAPWS-IF97) |
| Liquid surface temperature | 50.000 °C |
| Mass transfer coefficient | 0.005000 m/s |
| Surface area | 20.000 m² |
| Air relative humidity (water) | 60.000 % |
| Air temperature (water) | 30.000 °C |
| Vapour pressure at the surface (other liquid) | 10.000 kPa |
| Partial pressure in the air (other liquid) | 0 kPa |
| Molar mass (other liquid) | 58.080 kg/kmol |
Applying the formula below gives:
| Result | Value |
|---|---|
| Vapour pressure at the surface | 12.351 kPa |
| Partial pressure in the air | 2.5480 kPa |
| Evaporation flux | 3.2302e-04 kg/(m²·s) |
| Evaporation rate | 23.258 kg/h |
Open this example in the calculator and change any input.
Formula
\(N = k_c\frac{M}{R}\left(\frac{p_s}{T_s} - \frac{p_\infty}{T_a}\right), \quad \dot m = N A\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{liquid}\) | Liquid | - |
| \(T_s\) | Liquid surface temperature | K |
| \(k_c\) | Mass transfer coefficient | m/s |
| \(A\) | Surface area | m² |
| \(\varphi\) | Air relative humidity (water) | - |
| \(T_a\) | Air temperature (water) | K |
| \(p_v\) | Vapour pressure at the surface (other liquid) | Pa |
| \(p_\infty\) | Partial pressure in the air (other liquid) | Pa |
| \(M\) | Molar mass (other liquid) | kg/kmol |
| \(p_s\) | Vapour pressure at the surface | Pa |
| \(N\) | Evaporation flux | kg/(m²·s) |
| \(\dot m\) | Evaporation rate | kg/s |
Method and standards
Film theory.
Where it is used
- Hot wells, open tanks and drains.
- Solvent storage losses.
Common mistakes
- Air temperature for the surface.
- Ignoring humidity of the air.
Assumptions and limits
- Dilute vapour, steady state.
- For water the air-side concentration is taken at the air temperature; for another liquid the air temperature is not an input and the surface temperature is used for both.
- The mass transfer coefficient is your figure; the result is only as good as it is.
References
- Film mass transfer N = k_c (C_s − C_∞)
- C = pM/(RT); water vapour pressure from IAPWS-IF97
Questions and answers
20 m² of water at 50 °C in 30 °C, 60 % air, k_c 5 mm/s?
Roughly 23 kg/h of water.
Where does k_c come from?
Correlations with air speed over the surface; it is the main uncertainty.
Solvents?
Use their vapour pressure and molar mass; the result also feeds dilution ventilation.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.