Hot Water Boiler Circulation Flow

Water circulation flow through a hot water boiler or heater for its heat output and the supply and return temperatures, with IAPWS-IF97 enthalpies.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)BoilerPump

Inputs

Examples: 2 MW, 90/70 °C, 4 bar(a)High-temperature hot water 10 MW, 180/130 °C, 16 bar(a)500 kW, 80/60 °C, 3 bar(a)

Used for both enthalpies and the boiling margin: enter the lowest pressure the hot supply water sees (boiler outlet or pump suction).

Results

Water mass flow85,812kg/h
Water volume flow at the return temperature87.751m³/h
Mean specific heat (enthalpy difference over ΔT)4.1952kJ/(kg·K)
Margin of the supply below boiling53.613K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 MW, 90/70 °C, 4 bar(a). The inputs, in the units selected above:

InputValue
Boiler heat output2,000.0 kW
Supply (flow) temperature90.000 °C
Return temperature70.000 °C
Water pressure (absolute)4.0000 bar

Applying the formula below gives:

ResultValue
Water mass flow85,812 kg/h
Water volume flow at the return temperature87.751 m³/h
Mean specific heat (enthalpy difference over ΔT)4.1952 kJ/(kg·K)
Margin of the supply below boiling53.613 K

Open this example in the calculator and change any input.

Formula

\(\dot m = \frac{\dot Q}{h(T_s) - h(T_r)} \qquad \dot V = \frac{\dot m}{\rho(T_r)} \qquad \bar c_p = \frac{h(T_s) - h(T_r)}{T_s - T_r} \qquad \Delta T_{sub} = T_{sat}(p) - T_s\)

Variables

Symbol Meaning SI unit
\(\dot Q\) heat output W
\(T_s\) supply temperature K
\(T_r\) return temperature K
\(p\) water pressure Pa
\(\dot m\) mass flow kg/s
\(\dot V\) volume flow m³/s
\(\bar c_p\) mean specific heat J/(kg·K)
\(\Delta T_{sub}\) margin below boiling K

Method and standards

Energy balance with IAPWS-IF97 liquid enthalpies.

Where it is used

  • Hot water and HTHW boilers.
  • Process heating loops.
  • District heating.

Common mistakes

  • Mixing up flow and return.
  • Not pressurising HTHW enough.
  • Using the supply density for return-side pumps.

Assumptions and limits

  • Liquid water; boiler output as heat to the water.
  • One pressure is used for both enthalpies and the boiling margin; enter the lowest pressure at the hot supply (boiler outlet or pump suction).
  • The 15 K warning margin is a FireCAD rule of thumb, not a code value; follow the boiler maker's or the code's required margin.

References

  • IAPWS-IF97

Questions and answers

What flow does a 2 MW boiler need at 90/70 °C?

23.8 kg/s (85.8 t/h, about 88 m³/h at return temperature).

Why check the margin to boiling?

High-temperature hot water must stay well below saturation at the boiler outlet, or it flashes in the tubes and pumps.

Can I use 4.187 kJ/kgK?

Close at low temperatures; IF97 enthalpies are exact at any temperature and pressure.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.