FireCADCalc

Boiler Fuel Firing Rate

Fuel a boiler burns for a heat output or a steam flow, from the efficiency and the gross calorific value, with heat input and steam-to-fuel ratio.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationThermic fluid heatingPulp and paperFood, dairy and textileASME PTC 4 (fired steam generators)IAPWS-IF97 (water and steam)BoilerBurner and furnaceBoiler attendant and boiler operator examinations

This calculator is a step of the workflow Boiler: fuel to fans: enter the data once and each step feeds the next.

Inputs

Examples: Heat output 10 MW, coal 18.6 MJ/kg, efficiency 80 %Shell boiler 10 t/h, 10.5 bar(a) saturated, feed 105 °C, bagasse 9.7 MJ/kg, 68 %Water-tube 50 t/h, 66 bar(a) / 485 °C, feed 150 °C, fuel oil 42.5 MJ/kg, 88 %

Gross efficiency, on the gross (higher) calorific value, as ASME PTC 4 states it.

Heat output entered

Steam flow and conditions

At the boiler outlet. Absolute; choose a gauge unit to enter gauge readings.

Results

Fuel firing rate3,668.0kg/h
Heat input from fuel (on GCV)43,303kW
Heat output to steam38,107kW
Steam to fuel ratio13.631kg/kg
Steam enthalpy3,379.7kJ/kg
Feedwater enthalpy636.05kJ/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Heat output 10 MW, coal 18.6 MJ/kg, efficiency 80 %. The inputs, in the units selected above:

InputValue
Heat output fromHeat output entered
Heat output to steam10,000 kW
Steam generated10,000 kg/h
Steam pressure (absolute)10.500 bar
Steam conditionDry saturated
Steam temperature (superheated only)250.00 °C
Feedwater temperature105.00 °C
Boiler efficiency (on GCV)80.000 %
Gross calorific value of the fuel, as fired18,600 kJ/kg

Applying the formula below gives:

ResultValue
Fuel firing rate2,419.4 kg/h
Heat input from fuel (on GCV)12,500 kW
Heat output to steam10,000 kW

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_s \,(h_s - h_{fw}) \qquad \text{or} \qquad \dot Q = \dot Q_{out}\)

\(\dot Q_{in} = \frac{\dot Q}{\eta} \qquad \dot m_f = \frac{\dot Q}{\eta\;GCV} \qquad \text{steam to fuel ratio} = \frac{\dot m_s}{\dot m_f}\)

Variables

Symbol Meaning SI unit
\(\text{basis}\) heat output entered, or from the steam flow and conditions –
\(\dot Q_{out}\) heat output to steam, entered W
\(\dot m_s\) steam generated kg/s
\(p\) steam pressure at the boiler outlet, absolute Pa
\(\text{state}\) dry saturated or superheated steam –
\(T_s\) steam temperature (superheated) K
\(T_{fw}\) feedwater temperature K
\(\eta\) boiler efficiency on GCV –
\(GCV\) gross calorific value of the fuel as fired J/kg
\(\dot Q\) heat output to steam used W
\(\dot Q_{in}\) heat input from fuel, on GCV W
\(\dot m_f\) fuel firing rate kg/s
\(\dot m_s / \dot m_f\) steam to fuel ratio kg/kg
\(h_s\) steam enthalpy J/kg
\(h_{fw}\) feedwater enthalpy at the steam pressure J/kg

Method and standards

Energy balance on the boiler: the heat absorbed by the water and steam equals the fuel's heat input times the efficiency. Efficiency and calorific value are on the gross (higher) basis, as ASME PTC 4-2013 defines boiler efficiency. Steam and feedwater enthalpies come from FireCAD's IAPWS-IF97 implementation; blowdown is not included in the heat output (add it with the blowdown rate calculator if it is significant).

Where it is used

  • Sizing coal and biomass feeders, oil pumps and gas trains.
  • Fuel budgets and storage planning.
  • Estimating flue gas and ash quantities from the boiler duty.

Common mistakes

  • Using design efficiency for actual fuel consumption.
  • Mixing GCV with NCV-based efficiency.
  • Forgetting blowdown and losses when working from the steam output.

Assumptions and limits

  • Steady load; the efficiency entered applies at this load.
  • Heat output is the steam leaving the boiler minus the feedwater entering it; blowdown, soot-blowing steam and auxiliary steam are not included.
  • Feedwater enthalpy is taken at the steam pressure.
  • GCV as fired, on the same moisture basis as the fuel flow.

References

  • ASME PTC 4-2013 (efficiency on GCV)
  • IAPWS R7-97(2012) IF97

Questions and answers

How much fuel does a boiler burn?

Fuel = heat to steam ÷ (efficiency × GCV). A 10 t/h boiler making dry saturated steam at 10.5 bar(a) from 105 °C feedwater takes 6.49 MW; at 68 % efficiency on bagasse of 9.7 MJ/kg it burns 3.54 t/h.

Which calorific value goes with which efficiency?

Use the gross calorific value with an efficiency on GCV (ASME PTC 4 and most Indian practice). An efficiency stated on NCV (European practice) must be used with the NCV; mixing the two gives a fuel figure off by 5–10 % for coal and up to 20 % for wet biomass.

What is the steam-to-fuel ratio?

Steam generated per kg of fuel burnt, often called the evaporation ratio. It depends on the fuel's calorific value, so compare boilers on the same fuel or use the equivalent evaporation calculator.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.