FireCADCalc

Fuel Saving from Lower Flue Gas Temperature

Efficiency gain and fuel saved when the boiler exit gas temperature is lowered, from the fuel analysis, excess air and flue gas enthalpies.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileASME PTC 4 (fired steam generators)BoilerEconomiser and air preheaterStack and chimney

Inputs

Examples: Indian coal, 180 to 140 °C, 78 %Fuel oil, 250 to 180 °C, 84 %Bagasse, 200 to 160 °C, 68 %

Ultimate analysis, as fired, by mass

Keep it above the acid dew point (acid dew point calculator).

Results

Efficiency gain (points)1.9579%
Efficiency after79.958%
Fuel saved, share of present fuel2.4487%
Fuel saved293.84kg/h
Wet flue gas per kg of fuel8.4828kg/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Indian coal, 180 to 140 °C, 78 %. The inputs, in the units selected above:

InputValue
Carbon45.000 %
Hydrogen3.5000 %
Oxygen5.0000 %
Nitrogen1.0000 %
Sulphur0.50000 %
Ash35.000 %
Moisture10.000 %
Excess air25.000 %
Air humidity (kg water per kg dry air)0.013000 kg/kg
Gross calorific value of the fuel, as fired18,600 kJ/kg
Flue gas temperature now180.00 °C
Flue gas temperature after the improvement140.00 °C
Boiler efficiency now (on GCV)78.000 %
Fuel firing rate12,000 kg/h

Applying the formula below gives:

ResultValue
Efficiency gain (points)1.9579 %
Efficiency after79.958 %
Fuel saved, share of present fuel2.4487 %
Fuel saved293.84 kg/h
Wet flue gas per kg of fuel8.4828 kg/kg

Open this example in the calculator and change any input.

Formula

\(\Delta\eta = \frac{m_g\,\left[h_g(T_1) - h_g(T_2)\right]}{GCV} \qquad \eta_2 = \eta_1 + \Delta\eta\)

\(s = 1 - \frac{\eta_1}{\eta_2} \qquad \Delta\dot m_f = s\,\dot m_f\)

Variables

Symbol Meaning SI unit
\(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) ultimate analysis as fired, mass fractions –
\(EA\) excess air –
\(\omega\) air humidity, kg water per kg dry air kg/kg
\(GCV\) gross calorific value J/kg
\(T_1\) flue gas temperature now K
\(T_2\) flue gas temperature after the improvement K
\(\eta_1\) boiler efficiency now, on GCV –
\(\dot m_f\) fuel firing rate now kg/s
\(\Delta\eta\) efficiency gain –
\(\eta_2\) efficiency after –
\(s\) fuel saved, share of present fuel –
\(\Delta\dot m_f\) fuel saved kg/s
\(m_g\) wet flue gas per kg of fuel kg/kg
\(h_g\) enthalpy of the wet flue gas (Shomate integration) J/kg

Method and standards

Wet flue gas quantity and composition from FireCAD's exact-ratio combustion balance; gas enthalpy by integrating the NIST Shomate heat capacities of CO₂, H₂O, N₂, O₂, Ar and SO₂. The efficiency gain equals the drop in the flue gas loss (dry gas plus water vapour sensible heat), as in ASME PTC 4. Fuel saved for the same output is 1 − η₁/η₂.

Where it is used

  • Justifying an economiser, air heater or soot-blowing upgrade.
  • Setting the alarm level for a rising stack temperature (fouling).
  • Energy audits: putting a value on each 10 K of exit gas temperature.

Common mistakes

  • Subtracting efficiency points as fuel saved: 2 points from 78 % saves 2.45 % of fuel, not 2 %.
  • Reading the stack temperature after air ingress or dilution, which looks lower than the boiler exit.
  • Lowering the gas below the acid dew point to gain efficiency, then losing the air heater or economiser to corrosion.

Assumptions and limits

  • Same excess air and fuel before and after; only the exit gas temperature changes.
  • No condensation of water vapour (the gas stays above its water dew point); a warning appears below it.
  • The flue gas quantity is for the excess air entered, not a measured O₂; the GCV is checked against the Channiwala–Parikh estimate of the analysis (warning above 15 %).
  • A higher temperature after gives a negative gain, with a note.

References

  • ASME PTC 4-2013 §5.14 (dry gas and water vapour losses)
  • NIST Chemistry WebBook Shomate equations

Questions and answers

How much fuel does a lower flue gas temperature save?

For coal at 25 % excess air, cooling the exit gas from 180 to 140 °C raises efficiency by 1.96 points, from 78.0 to 80.0 %, and saves 2.45 % of the fuel. That is close to the rule of thumb of 1 % per 20 K.

How low can the flue gas go?

Above the acid dew point of the gas at the coldest metal, for any sulphur-bearing fuel; about 120–150 °C for coal and oil. Natural gas can go lower, and condensing equipment below the water dew point is a separate design.

What lowers the flue gas temperature?

Clean heating surfaces (soot blowing, water-side cleaning), an economiser or air heater, correct excess air, and stopping air ingress that bypasses the surfaces.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.