Worked example
Example: Indian coal, 180 to 140 °C, 78 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon | 45.000 % |
| Hydrogen | 3.5000 % |
| Oxygen | 5.0000 % |
| Nitrogen | 1.0000 % |
| Sulphur | 0.50000 % |
| Ash | 35.000 % |
| Moisture | 10.000 % |
| Excess air | 25.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Gross calorific value of the fuel, as fired | 18,600 kJ/kg |
| Flue gas temperature now | 180.00 °C |
| Flue gas temperature after the improvement | 140.00 °C |
| Boiler efficiency now (on GCV) | 78.000 % |
| Fuel firing rate | 12,000 kg/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Efficiency gain (points) | 1.9579 % |
| Efficiency after | 79.958 % |
| Fuel saved, share of present fuel | 2.4487 % |
| Fuel saved | 293.84 kg/h |
| Wet flue gas per kg of fuel | 8.4828 kg/kg |
Open this example in the calculator and change any input.
Formula
\(\Delta\eta = \frac{m_g\,\left[h_g(T_1) - h_g(T_2)\right]}{GCV} \qquad \eta_2 = \eta_1 + \Delta\eta\)
\(s = 1 - \frac{\eta_1}{\eta_2} \qquad \Delta\dot m_f = s\,\dot m_f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) | ultimate analysis as fired, mass fractions | – |
| \(EA\) | excess air | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(GCV\) | gross calorific value | J/kg |
| \(T_1\) | flue gas temperature now | K |
| \(T_2\) | flue gas temperature after the improvement | K |
| \(\eta_1\) | boiler efficiency now, on GCV | – |
| \(\dot m_f\) | fuel firing rate now | kg/s |
| \(\Delta\eta\) | efficiency gain | – |
| \(\eta_2\) | efficiency after | – |
| \(s\) | fuel saved, share of present fuel | – |
| \(\Delta\dot m_f\) | fuel saved | kg/s |
| \(m_g\) | wet flue gas per kg of fuel | kg/kg |
| \(h_g\) | enthalpy of the wet flue gas (Shomate integration) | J/kg |
Method and standards
Wet flue gas quantity and composition from FireCAD's exact-ratio combustion balance; gas enthalpy by integrating the NIST Shomate heat capacities of CO₂, H₂O, N₂, O₂, Ar and SO₂. The efficiency gain equals the drop in the flue gas loss (dry gas plus water vapour sensible heat), as in ASME PTC 4. Fuel saved for the same output is 1 − η₁/η₂.
Where it is used
- Justifying an economiser, air heater or soot-blowing upgrade.
- Setting the alarm level for a rising stack temperature (fouling).
- Energy audits: putting a value on each 10 K of exit gas temperature.
Common mistakes
- Subtracting efficiency points as fuel saved: 2 points from 78 % saves 2.45 % of fuel, not 2 %.
- Reading the stack temperature after air ingress or dilution, which looks lower than the boiler exit.
- Lowering the gas below the acid dew point to gain efficiency, then losing the air heater or economiser to corrosion.
Assumptions and limits
- Same excess air and fuel before and after; only the exit gas temperature changes.
- No condensation of water vapour (the gas stays above its water dew point); a warning appears below it.
- The flue gas quantity is for the excess air entered, not a measured O₂; the GCV is checked against the Channiwala–Parikh estimate of the analysis (warning above 15 %).
- A higher temperature after gives a negative gain, with a note.
References
- ASME PTC 4-2013 §5.14 (dry gas and water vapour losses)
- NIST Chemistry WebBook Shomate equations
Questions and answers
How much fuel does a lower flue gas temperature save?
For coal at 25 % excess air, cooling the exit gas from 180 to 140 °C raises efficiency by 1.96 points, from 78.0 to 80.0 %, and saves 2.45 % of the fuel. That is close to the rule of thumb of 1 % per 20 K.
How low can the flue gas go?
Above the acid dew point of the gas at the coldest metal, for any sulphur-bearing fuel; about 120–150 °C for coal and oil. Natural gas can go lower, and condensing equipment below the water dew point is a separate design.
What lowers the flue gas temperature?
Clean heating surfaces (soot blowing, water-side cleaning), an economiser or air heater, correct excess air, and stopping air ingress that bypasses the surfaces.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.