Fuel and Water Saving from Reduced Blowdown

Heat, fuel and water saved by lowering the boiler blowdown rate through better water treatment or automatic TDS control, per hour and per year.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)BoilerFlash vessel and condensate

Inputs

Examples: 10 t/h, 10.5 bar(a), blowdown 8 % to 4 %, coal50 t/h, 45 bar(a), 3 % to 1.5 %, oil20 t/h, 17.5 bar(a), 5 % to 2 %, bagasse

Results

Gross saving with no blowdown heat recovery; if a flash vessel and cooler already recover blowdown heat, the real saving is smaller. Blowdown is a share of steam: a share of feedwater b_fw converts as b = b_fw / (1 − b_fw).

Fuel saved9.1316kg/h
Fuel saved per year73.053t
Treated water saved per year3,200.0t
Heat no longer blown down36.801kW
Heat per kg of blowdown above feedwater331.20kJ/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 t/h, 10.5 bar(a), blowdown 8 % to 4 %, coal. The inputs, in the units selected above:

InputValue
Steam generated10,000 kg/h
Blowdown now, as a share of steam8.0000 %
Blowdown after, as a share of steam4.0000 %
Drum pressure (absolute)10.500 bar
Feedwater temperature105.00 °C
Boiler efficiency (on GCV)78.000 %
Gross calorific value of the fuel, as fired18,600 kJ/kg
Operating hours per year8,000.0 h

Applying the formula below gives:

ResultValue
Fuel saved9.1316 kg/h
Fuel saved per year73.053 t
Treated water saved per year3,200.0 t
Heat no longer blown down36.801 kW
Heat per kg of blowdown above feedwater331.20 kJ/kg

Open this example in the calculator and change any input.

Formula

\(\Delta\dot Q = S\,(b_1 - b_2)\,(h_f - h_{fw}) \qquad \Delta\dot m_f = \frac{\Delta\dot Q}{\eta_1\,GCV}\)

\(\Delta m_f = \Delta\dot m_f\,t_{op} \qquad \Delta m_w = S\,(b_1 - b_2)\,t_{op}\)

Variables

Symbol Meaning SI unit
\(S\) steam generated kg/s
\(b_1\) blowdown now, share of steam –
\(b_2\) blowdown after, share of steam –
\(p\) drum pressure, absolute Pa
\(T_{fw}\) feedwater temperature K
\(\eta_1\) boiler efficiency on GCV –
\(GCV\) gross calorific value J/kg
\(t_{op}\) operating hours per year s
\(\Delta\dot m_f\) fuel saved kg/s
\(\Delta m_f\) fuel saved per year kg
\(\Delta m_w\) water saved per year kg
\(\Delta\dot Q\) heat no longer blown down W
\(h_f - h_{fw}\) heat per kg of blowdown above feedwater J/kg
\(h_f\) saturated water enthalpy at drum pressure J/kg
\(h_{fw}\) feedwater enthalpy J/kg

Method and standards

Blowdown leaves the drum as saturated water; each kg was heated from the feedwater temperature. Enthalpies by FireCAD's IAPWS-IF97; fuel from the boiler efficiency on GCV.

Where it is used

  • Justifying automatic TDS (conductivity) blowdown control.
  • Valuing better make-up treatment or more condensate return.
  • Water audits: blowdown is often the largest controllable water loss of a boiler house.

Common mistakes

  • Expressing blowdown as a share of feedwater in one place and of steam in another.
  • Lowering blowdown below what the water chemistry needs, causing carry-over or deposits.
  • Ignoring heat already recovered from blowdown.

Assumptions and limits

  • No blowdown heat recovery; same steam output and efficiency.
  • Water saved counted as treated make-up water; the treatment chemicals saved are in proportion but not calculated.
  • Blowdown is a share of steam. If yours is quoted as a share of feedwater \(b_{fw}\), convert with \(b = b_{fw} / (1 - b_{fw})\).
  • With existing blowdown heat recovery the saving is smaller than shown; a note on the result says so.

References

  • IAPWS R7-97(2012) IF97
  • first law heat balance

Questions and answers

How much does reducing blowdown save?

A 10 t/h boiler at 10.5 bar(a) cutting blowdown from 8 to 4 % of steam stops 400 kg/h of water at 182 °C leaving the drum: 36.8 kW of heat, 9.1 kg/h of coal at 78 % efficiency and 18.6 MJ/kg, 73 t of coal and 3200 t of treated water in 8000 hours.

How do I lower blowdown safely?

Improve the make-up treatment (softener, RO, dealkaliser), return more condensate, and control blowdown by conductivity (TDS) instead of a fixed valve opening. Keep the boiler water within the limits of the boiler maker or the water chemistry standard.

What if blowdown heat is already recovered?

Then the saving is smaller: a flash vessel and heat exchanger already recover much of the heat. This calculator gives the gross saving with no recovery.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.