Worked example
Example: Atrazine 0.01 mg/L, K 40, 1/n 0.30, 480 g/L, 1,000 L/min, 15 min. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Influent concentration | 0.010000 mg/L |
| Freundlich capacity, (mg/g)(L/mg)^(1/n) | 40.000 - |
| Freundlich intensity 1/n | 0.30000 - |
| GAC bed density | 480.00 kg/m³ |
| Flow | 1,000.0 L/min |
| Empty-bed contact time | 15.000 min |
Applying the formula below gives:
| Result | Value |
|---|---|
| Equilibrium carbon loading | 10.048 |
| Carbon usage rate (minimum) | 9.9527e-04 g/L |
| Specific throughput | 1,004.8 L/g |
| Bed volume | 15.000 m³ |
| Carbon in the bed | 7,200.0 kg |
| Water treated to breakthrough (ideal) | 7,234,233 m³ |
| Bed life (ideal) | 5,023.8 d |
| Bed volumes treated | 482,282 |
Open this example in the calculator and change any input.
Formula
\(q_e = KC_0^{1/n}, \quad CUR = \frac{C_0}{q_e}\)
\(M_{GAC} = Q\cdot EBCT\cdot\rho_b, \quad V_t = \frac{M_{GAC}}{CUR}, \quad t_{bed} = \frac{V_t}{Q}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_0\) | Influent concentration | kg/m³ |
| \(K\) | Freundlich capacity, (mg/g)(L/mg)^(1/n) | - |
| \(1/n\) | Freundlich intensity 1/n | - |
| \(\rho_b\) | GAC bed density | kg/m³ |
| \(Q\) | Flow | m³/s |
| \(EBCT\) | Empty-bed contact time | s |
| \(q_e\) | Equilibrium carbon loading | - |
| \(CUR\) | Carbon usage rate (minimum) | kg/m³ |
| \(1/CUR\) | Specific throughput | m³/kg |
| \(V_b\) | Bed volume | m³ |
| \(M_{GAC}\) | Carbon in the bed | kg |
| \(V_t\) | Water treated to breakthrough (ideal) | m³ |
| \(t_{bed}\) | Bed life (ideal) | s |
| \(BV\) | Bed volumes treated | - |
Method and standards
Equilibrium (ideal) carbon usage from the Freundlich isotherm.
Where it is used
- Screening GAC for groundwater VOCs.
- Estimating carbon replacement frequency.
Common mistakes
- Using isotherm constants with different units of C.
- Treating the ideal bed life as the design bed life.
Assumptions and limits
- Single solute, equilibrium loading at the influent concentration, no mass transfer zone.
Questions and answers
What EBCT is usual?
10–20 minutes for taste, odour and synthetic organics; longer for NOM or DBP precursor removal.
Why is the real CUR higher?
Competitive adsorption by NOM, preloading and the length of the mass transfer zone mean carbon is replaced before it reaches equilibrium.
What do the defaults represent?
An illustrative case: Atrazine 0.01 mg/L, K 40, 1/n 0.30, 480 g/L, 1,000 L/min, 15 min. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 15-6, eqs. 15-108 and 15-109 and Example 15-9