FireCADCalc

Chick–Watson Disinfection: Log Inactivation and Required CT

Log inactivation of a microorganism from disinfectant concentration and contact time by the Chick–Watson law, and the time and CT for a target log inactivation.

Inputs

Examples: Free chlorine on a virus, k 2.0 (L/mg)/min, n 1, 1 mg/L, 6 min, 4-logChloramine, n 1.2, k 0.03, 2.5 mg/L for 60 min, 2-log

Accepted: 1E-6 to 10,000
Accepted: 0.1 to 5
Accepted: 0.001 to 100 mg/L
Accepted: 0.0016667 to 16,667 min
Accepted: 0.1 to 10

Results

Ct in mg·min/L. Chick–Watson assumes first-order die-off at constant residual; many organisms show a lag (shoulder) or tailing, and regulatory CT tables already include safety factors.

Natural log of survival-5.4051
Log inactivation2.3474
Concentration times time150.00
Time for the target log inactivation51.121min
Ct for the target (n = 1 basis)127.80

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Free chlorine on a virus, k 2.0 (L/mg)/min, n 1, 1 mg/L, 6 min, 4-log. The inputs, in the units selected above:

InputValue
Coefficient of specific lethality, (L/mg)ⁿ per min2.0000 -
Coefficient of dilution (usually close to 1)1.0000 -
Disinfectant residual1.0000 mg/L
Contact time (T10 for a real contactor)6.0000 min
Target log inactivation4.0000 -

Applying the formula below gives:

ResultValue
Natural log of survival-12.000
Log inactivation5.2115
Concentration times time6.0000
Time for the target log inactivation4.6052 min
Ct for the target (n = 1 basis)4.6052

Open this example in the calculator and change any input.

Formula

\(\ln\frac{N}{N_0} = -\Lambda_{CW}C^nt\)

\(t_{req} = \frac{2.303\,\log_{target}}{\Lambda_{CW}C^n}\)

Variables

Symbol Meaning SI unit
\(\Lambda_{CW}\) Coefficient of specific lethality, (L/mg)ⁿ per min -
\(n\) Coefficient of dilution (usually close to 1) -
\(C\) Disinfectant residual kg/m³
\(t\) Contact time (T10 for a real contactor) s
\(\log_{target}\) Target log inactivation -
\(\ln(N/N_0)\) Natural log of survival -
\(\log_{10}(N_0/N)\) Log inactivation -
\(Ct\) Concentration times time -
\(t_{req}\) Time for the target log inactivation s
\((Ct)_{req}\) Ct for the target (n = 1 basis) -

Method and standards

Chick–Watson disinfection kinetics.

Where it is used

  • Estimating contact time from bench inactivation data.
  • Comparing disinfectants.

Common mistakes

  • Mixing seconds and minutes in k.
  • Using base-10 logs in the natural-log equation.

Assumptions and limits

  • Constant residual; first-order die-off without lag or tailing.

Questions and answers

What does n mean?

The dilution coefficient: n > 1 means concentration matters more than time, n < 1 the reverse; with n = 1 only the product Ct matters.

Why use T10?

In a real contactor 10 % of the water passes faster than T10, so using it protects the fastest water.

What do the defaults represent?

An illustrative case: Free chlorine on a virus, k 2.0 (L/mg)/min, n 1, 1 mg/L, 6 min, 4-log. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 13-2, eq. 13-4 and Example 13-1

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.