FireCADCalc

Breakpoint Chlorination Dose for Ammonia

Chlorine dose to pass breakpoint for a given ammonia nitrogen, with ammonia oxidised to nitrogen gas or to nitrate, plus other demand and the free residual wanted.

Inputs

Examples: Groundwater 0.4 mg/L N, 0.8 demand, 0.5 residual, 2,500 m3/d

Accepted: 0 to 100 mg/L
Accepted: 0 to 100 mg/L
Accepted: 0 to 10 mg/L
Accepted: 0.864 to 8,640,000 m³/d

Results

Stoichiometric. In practice breakpoint needs about 8–10 mg Cl₂ per mg NH₃-N because some ammonia goes to nitrate and other side products; check by a bench breakpoint curve.

Chlorine to ammonia-N mass ratio7.5926
Chlorine to reach breakpoint3.0371mg/L
Total chlorine dose4.3371mg/L
Chlorine feed10.843kg/d

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Groundwater 0.4 mg/L N, 0.8 demand, 0.5 residual, 2,500 m3/d. The inputs, in the units selected above:

InputValue
Ammonia nitrogen0.40000 mg/L
Ammonia end productNitrogen gas (3 HOCl per 2 NH3)
Other chlorine demand (iron, manganese, organics)0.80000 mg/L
Free chlorine residual wanted0.50000 mg/L
Flow2,500.0 m³/d

Applying the formula below gives:

ResultValue
Chlorine to ammonia-N mass ratio7.5926
Chlorine to reach breakpoint3.0371 mg/L
Total chlorine dose4.3371 mg/L
Chlorine feed10.843 kg/d

Open this example in the calculator and change any input.

Formula

\(2\text{NH}_3 + 3\text{HOCl} \rightarrow \text{N}_2 + 3\text{H}_2\text{O} + 3\text{HCl}, \quad \frac{\text{Cl}_2}{\text{N}} = \frac{1.5\times70.9}{14.007} = 7.6\)

\(\text{NH}_3 + 4\text{HOCl} \rightarrow \text{NO}_3^- + \text{H}_2\text{O} + \text{H}^+ + 4\text{HCl}, \quad D = R\,[\text{NH}_3\text{-N}] + D_{other} + C_{free}\)

Variables

Symbol Meaning SI unit
\(NH_3\text{-}N\) Ammonia nitrogen kg/m³
\(\text{route}\) Ammonia end product -
\(D_{other}\) Other chlorine demand (iron, manganese, organics) kg/m³
\(C_{free}\) Free chlorine residual wanted kg/m³
\(Q\) Flow m³/s
\(Cl_2:N\) Chlorine to ammonia-N mass ratio -
\(D_{bp}\) Chlorine to reach breakpoint kg/m³
\(D\) Total chlorine dose kg/m³
\(\dot m\) Chlorine feed kg/s

Method and standards

Stoichiometry of breakpoint chlorination.

Where it is used

  • Free-chlorine conversion of chloraminated or ammonia-bearing waters.
  • Chlorine supply sizing.

Common mistakes

  • Using NH₃ instead of NH₃-N in the ratio.
  • Expecting the stoichiometric dose to be enough in practice.

Assumptions and limits

  • Stoichiometric minimum; pH 7–8.

Questions and answers

Why does chlorine fall before the breakpoint?

Chlorine first forms chloramines with ammonia, then oxidises them; the combined residual falls to a minimum (the breakpoint) beyond which free chlorine appears.

Which route uses less chlorine?

To nitrogen gas: 7.6 mg Cl₂ per mg N against 20.2 for nitrate.

What do the defaults represent?

An illustrative case: Groundwater 0.4 mg/L N, 0.8 demand, 0.5 residual, 2,500 m3/d. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 13-5, eqs. 13-25 and 13-26 and Example 13-6

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.