Worked example
Example: Illustrative kitchen at 60 L/min. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Peak flow from fixtures | 60.000 L/min |
| Retention time | 30.000 min |
| Storage factor for grease and solids | 1.2500 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Working volume | 2,250.0 L |
| Volume without the storage factor | 1,800.0 L |
Open this example in the calculator and change any input.
Formula
\(V = k_s\,\dot V\,t_r\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Peak flow from fixtures | m³/s |
| \(t_r\) | Retention time | s |
| \(k_s\) | Storage factor for grease and solids | - |
| \(V\) | Working volume | m³ |
| \(V_h\) | Volume without the storage factor | m³ |
Method and standards
Grease trap.
Where it is used
- Restaurants, hotels and canteens.
- Food factory drainage.
Common mistakes
- Sizing on average instead of peak flow.
- Neglecting cleaning frequency.
Assumptions and limits
- Peak flow and retention as entered.
References
- Retention-time sizing of grease interceptors
Questions and answers
How big a grease trap for 60 L/min peak flow?
About 2,250 litres with 30 min retention and a 1.25 storage factor.
Why does retention time matter?
Grease needs time to float; too small a trap lets it pass to the sewer.
What do the defaults represent?
An illustrative kitchen with 60 L/min peak flow, 30 min retention and storage factor 1.25.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.