Worked example
Example: Paved yard 2 ha, C 0.85, 50 mm/h, 1 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Runoff coefficient | 85.000 % |
| Rainfall intensity for the design storm | 50.000 mm/h |
| Catchment area | 2.0000 ha |
| Storm duration | 1.0000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Peak runoff | 0.23611 m³/s |
| Runoff volume over the storm | 850.00 m³ |
Open this example in the calculator and change any input.
Formula
\(Q = C\, i\, A\)
\(V = Q\, t\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\) | runoff coefficient | - |
| \(i\) | rainfall intensity | m/s |
| \(A\) | catchment area | m² |
| \(t\) | storm duration | s |
| \(Q\) | peak runoff | m³/s |
| \(V\) | runoff volume | m³ |
Method and standards
The rational method takes peak runoff as the share C of rainfall intensity falling on the catchment area. In SI units with i in m/s and A in m², Q comes out in m³/s.
Where it is used
- Sizing plant storm drains, sumps and pumps.
- Checking coal yard and ash pond runoff.
- Planning rainwater harvesting.
Common mistakes
- Mixing units (mm/h with hectares needs conversion).
- Using a 24-hour average intensity for a short time of concentration.
- Applying it to large catchments.
Assumptions and limits
- Small catchments; uniform rain over the area.
- The volume V = Q t holds the peak rate for the whole storm. For the volume, enter the intensity for a storm of duration t (from the IDF data); using the time-of-concentration intensity with a longer duration overstates the volume.
References
- Rational method
Questions and answers
What runoff comes from 2 ha of paving in a 50 mm/h storm?
About 0.24 m³/s with C 0.85, and 850 m³ over one hour.
What runoff coefficient should I use?
Near 1 for roofs and paving, much lower for lawns and open ground; use local guidance for the surfaces.
Which rainfall intensity?
The intensity for a storm lasting the catchment's time of concentration at the chosen return period, from local rainfall data.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.