Worked example
Example: 120 L/s at 1 in 250, 450 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Design flow | 120.00 L/s |
| Manning roughness | 0.013000 - |
| Pipe slope | 0.40000 % |
| Chosen diameter (0 to use the size found) | 450.00 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Diameter running just full | 386.27 mm |
| Full-bore capacity of the chosen pipe | 180.32 L/s |
| Depth ratio at the design flow | 59.630 % |
| Velocity at the design flow | 1.2133 m/s |
Open this example in the calculator and change any input.
Formula
\(D_{full} = \left(\frac{4^{5/3} Q n}{\pi\sqrt{S}}\right)^{3/8}, \quad Q = \frac{1}{n} A R^{2/3} S^{1/2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Design flow | m³/s |
| \(n\) | Manning roughness | - |
| \(S\) | Pipe slope | - |
| \(D_c\) | Chosen diameter (0 to use the size found) | m |
| \(D_{full}\) | Diameter running just full | m |
| \(Q_f\) | Full-bore capacity of the chosen pipe | m³/s |
| \(y/D\) | Depth ratio at the design flow | - |
| \(v\) | Velocity at the design flow | m/s |
Method and standards
Manning.
Where it is used
- Plant drains and sewers.
- Storm water pipes.
Common mistakes
- n from the wrong material.
- Designing to the 0.94 D peak.
Assumptions and limits
- Uniform steady flow.
- The calculator does not pick a standard size: enter the next available size above D_full as the chosen diameter to get its capacity, depth and velocity.
References
- Manning's equation for circular conduits
- full and part full
Questions and answers
120 L/s at 1 in 250, n 0.013?
About 390 mm running full; a 450 mm pipe runs about 60 % deep at 1.2 m/s.
Why design part full?
Room for peaks and ventilation; many standards limit depth.
Self-cleansing?
Keep the velocity above your standard's minimum, often 0.6 to 0.8 m/s.