Worked example
Example: Unconfined, 20 m saturated. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Aquifer | Unconfined (water table) |
| Hydraulic conductivity | 2.0000e-04 m/s |
| Aquifer thickness (confined) or saturated thickness (unconfined) | 20.000 m |
| Drawdown at the well | 4.0000 m |
| Well radius | 150.00 mm |
| Radius of influence | 300.00 m |
| Confined only: static head above the top of the aquifer (0 = not checked) | 0 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Well yield | 42.853 m³/h |
| Sichardt estimate of the radius of influence 3000 s √K | 169.71 m |
Open this example in the calculator and change any input.
Formula
\(Q = \frac{2\pi K b s_w}{\ln(R/r_w)} \ \text{(confined)}, \quad Q = \frac{\pi K (H^2 - h_w^2)}{\ln(R/r_w)} \ \text{(unconfined)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{aquifer}\) | Aquifer | - |
| \(K\) | Hydraulic conductivity | m/s |
| \(b / H\) | Aquifer thickness (confined) or saturated thickness (unconfined) | m |
| \(s_w\) | Drawdown at the well | m |
| \(r_w\) | Well radius | m |
| \(R\) | Radius of influence | m |
| \(h_c\) | Confined: static head above the top of the aquifer (0 = not checked) | m |
| \(h_w\) | Unconfined: water depth in the well, H − s_w | m |
| \(Q\) | Well yield | m³/s |
| \(R_S\) | Sichardt estimate of the radius of influence 3000 s √K | m |
Method and standards
Radial steady flow.
Where it is used
- Plant water supply wells.
- Dewatering.
Common mistakes
- Unconfined formula with drawdown instead of heads.
- Ignoring well losses.
Assumptions and limits
The confined equation holds only while the water level stays above the top of the aquifer. Enter the static head above the aquifer top to have the page warn when the drawdown exceeds it.
Steady, homogeneous, fully penetrating well.
References
- Thiem (1906) steady radial flow; Dupuit–Forchheimer for unconfined aquifers; Sichardt radius of influence (empirical)
Questions and answers
Unconfined, K 2e-4 m/s, 20 m thick, 4 m drawdown?
About 43 m³/h with R 300 m.
Does R matter much?
Only through its logarithm, so a rough R is fine.
Steady state?
Thiem assumes pumping has gone on long enough for steady flow.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.