Worked example
Example: Four-pipe loop, Hazen–Williams. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Head-loss exponent (1.852 Hazen–Williams, 2 Darcy) | 1.8520 - |
| Resistance pipe 1 (h = rQ^n, SI) | 500.00 - |
| Assumed flow pipe 1 (clockwise +) | 0.060000 m³/s |
| Resistance pipe 2 | 800.00 - |
| Assumed flow pipe 2 | 0.030000 m³/s |
| Resistance pipe 3 | 600.00 - |
| Assumed flow pipe 3 | -0.040000 m³/s |
| Resistance pipe 4 | 1,200.0 - |
| Assumed flow pipe 4 | -0.020000 m³/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Balanced flow pipe 1 | 0.055097 m³/s |
| Balanced flow pipe 2 | 0.025097 m³/s |
| Balanced flow pipe 3 | -0.044903 m³/s |
| Balanced flow pipe 4 | -0.024903 m³/s |
| Total loop correction | -0.004903 m³/s |
| Head loss in pipe 1 | 2.3310 m |
Open this example in the calculator and change any input.
Formula
\(\Delta Q = -\frac{\sum rQ|Q|^{n - 1}}{n\sum r|Q|^{n - 1}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Head-loss exponent (1.852 Hazen–Williams, 2 Darcy) | - |
| \(r_1\) | Resistance pipe 1 (h = rQ^n, SI) | - |
| \(Q_1\) | Assumed flow pipe 1 (clockwise +) | m³/s |
| \(r_2\) | Resistance pipe 2 | - |
| \(Q_2\) | Assumed flow pipe 2 | m³/s |
| \(r_3\) | Resistance pipe 3 | - |
| \(Q_3\) | Assumed flow pipe 3 | m³/s |
| \(r_4\) | Resistance pipe 4 | - |
| \(Q_4\) | Assumed flow pipe 4 | m³/s |
| \(Q_1'\) | Balanced flow pipe 1 | m³/s |
| \(Q_2'\) | Balanced flow pipe 2 | m³/s |
| \(Q_3'\) | Balanced flow pipe 3 | m³/s |
| \(Q_4'\) | Balanced flow pipe 4 | m³/s |
| \(\Delta Q\) | Total loop correction | m³/s |
| \(h_1\) | Head loss in pipe 1 | m |
Method and standards
Hardy Cross correction.
Where it is used
- Plant water and fire-water ring mains.
- Teaching network analysis.
Common mistakes
- Assumed flows violating continuity.
- Inconsistent sign convention.
Assumptions and limits
- Single loop; fixed resistances.
- Resistances r are in SI (h in m, Q in m³/s, h = rQⁿ); flows may be entered in any flow unit and are converted to m³/s.
- The iteration must converge (|ΔQ| below 10⁻¹² of the flows) or the page reports failure.
References
- Hardy Cross (1936) method of balancing heads (Streeter and Wylie, Fluid Mechanics, ch. 11)
Questions and answers
Why must head losses sum to zero?
Going round a loop you return to the same point, so the net change in head is zero.
Why do assumed flows need continuity?
The loop correction adds the same ΔQ to every pipe, which keeps junction balances but cannot fix them.
What do the defaults represent?
A four-pipe loop with assumed flows that already balance at the junctions.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.