FireCADCalc

Detention Storage Volume (Modified Rational Method)

Storage volume of a detention pond or tank so that outflow is limited to a set rate, by the modified rational method over the critical storm duration.

Inputs

Examples: 5 ha site, 0.25 m3/s allowed2 ha paved, tight outflow

Rainfall intensity

Results

The rainfall constants a, b and n come from your local intensity–duration–frequency curve for the chosen return period.

Critical storm duration194.28min
Intensity at the critical duration40.958mm/h
Peak inflow C i A0.45509m³/s
Storage volume needed3,772.7m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 ha site, 0.25 m3/s allowed. The inputs, in the units selected above:

InputValue
Runoff coefficient80.000 %
Catchment area5.0000 ha
Time of concentration10.000 min
Allowed outflow0.25000 m³/s
Rainfall curve i = a/(t + b)^n: a (mm/h with t in min)3,000.0 -
b (minutes)20.000 -
n0.80000 -

Applying the formula below gives:

ResultValue
Critical storm duration194.28 min
Intensity at the critical duration40.958 mm/h
Peak inflow C i A0.45509 m³/s
Storage volume needed3,772.7 m³

Open this example in the calculator and change any input.

Formula

\(V(t_d) = C\, i(t_d)\, A\, t_d - \frac{Q_o (t_d + t_c)}{2}, \quad i = \frac{a}{(t + b)^n}, \quad V = \max_{t_d} V(t_d)\)

Variables

Symbol Meaning SI unit
\(C\) Runoff coefficient -
\(A\) Catchment area m²
\(t_c\) Time of concentration s
\(Q_o\) Allowed outflow m³/s
\(a\) Rainfall curve i = a/(t + b)^n: a (mm/h with t in min) -
\(b\) b (minutes) -
\(n\) n -
\(t_d\) Critical storm duration s
\(i\) Intensity at the critical duration m/s
\(Q_i\) Peak inflow C i A m³/s
\(V\) Storage volume needed m³

Method and standards

Modified rational method.

Where it is used

  • Plant storm water ponds.
  • Roof and yard detention tanks.

Common mistakes

  • Intensity units.
  • Using it for large catchments.

Assumptions and limits

  • Small catchments, linear outflow rise.
  • Durations from t_c to 24 h are searched; a maximum at the 24-hour limit is flagged as a lower bound.

References

  • Modified rational method V = Q_i t_d − ½Q_o(t_d + t_c) (FHWA HEC-22 practice); intensity curve i = a/(t + b)^n

Questions and answers

What does the default site need?

A 5 ha site at C 0.8 limited to 0.25 m³/s needs about 3,800 m³; the critical storm lasts about 3¼ hours.

Why search over durations?

Longer storms have less intensity but more volume; the worst one sets the storage.

Large catchments?

Use a hydrograph routing method instead.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.