Kitchen Grease Trap Sizing

Working volume of a kitchen grease trap from the peak flow of the connected sinks and appliances, the retention time and a storage factor for grease.

Inputs

Examples: Illustrative kitchen at 60 L/minSmall restaurantHotel kitchen

Accepted: 0.6 to 3,000 L/min
Accepted: 1 to 120 min
Accepted: 1 to 3

Results

Grease separates by floating, so the trap must hold the incoming flow long enough for fat droplets to rise: about 20–30 minutes at peak flow. The storage factor adds room for the grease and food solids that collect between cleanings. Hot water and detergents keep grease emulsified and reduce separation; cool the flow and clean the trap regularly. Check local plumbing codes, which may use fixture-unit methods instead.

Working volume6,750.0L
Volume without the storage factor4,500.0L

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative kitchen at 60 L/min. The inputs, in the units selected above:

InputValue
Peak flow from fixtures60.000 L/min
Retention time30.000 min
Storage factor for grease and solids1.2500 -

Applying the formula below gives:

ResultValue
Working volume2,250.0 L
Volume without the storage factor1,800.0 L

Open this example in the calculator and change any input.

Formula

\(V = k_s\,\dot V\,t_r\)

Variables

Symbol Meaning SI unit
\(\dot V\) Peak flow from fixtures m³/s
\(t_r\) Retention time s
\(k_s\) Storage factor for grease and solids -
\(V\) Working volume m³
\(V_h\) Volume without the storage factor m³

Method and standards

Grease trap.

Where it is used

  • Restaurants, hotels and canteens.
  • Food factory drainage.

Common mistakes

  • Sizing on average instead of peak flow.
  • Neglecting cleaning frequency.

Assumptions and limits

  • Peak flow and retention as entered.

References

  • Retention-time sizing of grease interceptors

Questions and answers

How big a grease trap for 60 L/min peak flow?

About 2,250 litres with 30 min retention and a 1.25 storage factor.

Why does retention time matter?

Grease needs time to float; too small a trap lets it pass to the sewer.

What do the defaults represent?

An illustrative kitchen with 60 L/min peak flow, 30 min retention and storage factor 1.25.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.