Travelling Grate Speed and Residence Time

Speed of a travelling or chain grate stoker from the fuel feed, bulk density, grate width and fuel bed depth, with the fuel's residence time on the grate.

Process steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileBoiler

Inputs

Examples: Coal 4 t/h, 800 kg/m³, 3 m wide, 150 mm bed, 6 m activeCoal 10 t/h, 850, 5 m, 180 mm, 8 mBiomass chips 6 t/h, 300, 4 m, 300 mm, 7 m

Results

The fuel must burn out within the residence time; the time needed depends on the fuel and is set by the stoker maker.

Grate speed0.18519m/min
Residence time on the grate32.400min

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Coal 4 t/h, 800 kg/m³, 3 m wide, 150 mm bed, 6 m active. The inputs, in the units selected above:

InputValue
Fuel feed rate4,000.0 kg/h
Bulk density of the fuel on the grate800.00 kg/m³
Effective grate width3.0000 m
Fuel bed depth at the gate150.00 mm
Active grate length6.0000 m

Applying the formula below gives:

ResultValue
Grate speed0.18519 m/min
Residence time on the grate32.400 min

Open this example in the calculator and change any input.

Formula

\(v = \frac{\dot m_f}{\rho_b\,W\,\delta} \qquad t = \frac{L}{v}\)

Variables

Symbol Meaning SI unit
\(\dot m_f\) fuel feed kg/s
\(\rho_b\) fuel bulk density kg/m³
\(W\) grate width m
\(\delta\) bed depth m
\(L\) active grate length m
\(v\) grate speed m/s
\(t\) residence time s

Method and standards

Continuity: the fuel volume fed equals bed cross-section times grate speed.

Where it is used

  • Setting grate speed for a load.
  • Checking a grate for a new fuel.
  • Explaining unburned carbon in grate ash.

Common mistakes

  • Using the density of the fuel lump, not the bulk density.
  • Using the full grate length when part of it is ignition or burnout zone.
  • Ignoring the bed shrinking as fuel burns.

Assumptions and limits

  • Uniform bed depth across the width; no slip of the bed on the grate.

References

  • Continuity of the fuel bed on the grate

Questions and answers

How fast should a travelling grate move?

Fast enough to carry the fuel fed. 4 t/h of coal at 800 kg/m³ on a 3 m grate with a 150 mm bed needs 0.19 m/min; on a 6 m active length the coal spends 32 minutes on the grate.

Deeper bed or faster grate?

For the same feed, a deeper bed lets the grate run slower and gives more burning time, but too deep a bed burns poorly; the stoker maker gives the range for the fuel.

What if unburned fuel reaches the ash pit?

The residence time is too short: slow the grate and thin the bed, or check the air distribution.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.