Worked example
Example: 12 t/h coal, 12 h, 0.8 t/m³, 85 % usable, 2 bunkers. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fuel firing rate at MCR | 12,000 kg/h |
| Hours of firing to store | 12.000 h |
| Bulk density of the fuel | 800.00 kg/m³ |
| Usable share of the geometric volume | 85.000 % |
| Number of bunkers sharing the storage | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total geometric volume | 211.76 m³ |
| Geometric volume of each bunker | 105.88 m³ |
| Volume of fuel stored | 180.00 m³ |
| Mass of fuel stored | 144.00 t |
Open this example in the calculator and change any input.
Formula
\(m = \dot m_f\,t_s \qquad V_f = \frac{m}{\rho_b} \qquad V_t = \frac{V_f}{f} \qquad V_1 = \frac{V_t}{n}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_f\) | fuel firing rate at MCR | kg/s |
| \(t_s\) | hours of firing to store | s |
| \(\rho_b\) | bulk density of the fuel | kg/m³ |
| \(f\) | usable share of the geometric volume | – |
| \(n\) | number of bunkers | – |
| \(V_t\) | total geometric volume | m³ |
| \(V_1\) | geometric volume of each bunker | m³ |
| \(V_f\) | volume of fuel stored | m³ |
| \(m\) | mass of fuel stored | kg |
Method and standards
Mass and volume balance on the bunkers at the MCR firing rate.
Where it is used
- Sizing coal bunkers and silos for boilers.
- Setting bunker fill schedules.
- Checking hours of storage after a fuel change.
Common mistakes
- Using a coal bulk density that ignores moisture.
- Counting the whole geometric volume as usable.
- Ignoring the hopper cone in the volume.
Assumptions and limits
- Bulk density as stored; wet or fine coal and compacted biomass differ from the loose value.
- Storage time and usable share are your inputs; the calculator does not suggest them.
References
- Mass and volume balance
Questions and answers
How big a bunker does a boiler need?
Volume = firing rate × hours ÷ bulk density ÷ usable share. 12 t/h of coal for 12 hours at 0.8 t/m³ is 180 m³ of coal; with 85 % of the bunker usable, 212 m³ in total, 106 m³ each for two bunkers.
Why is bagasse storage so much bigger?
Its bulk density is about one seventh of coal's. Two hours of bagasse at 25 t/h, at a bulk density of 0.12 t/m³ with 80 % of the bin usable, needs about 520 m³ of bin.
What does the usable share cover?
The hopper, the cone of the material at the top (angle of repose) and dead zones that do not flow. Use the share for your bunker shape.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.