FireCADCalc

Grate Ash Quench Water

Heat to remove from hot grate or bottom ash and the quench water flow for a water temperature rise, with ash specific heat 0.2 Btu/lb·°F by default.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolBoiler

Inputs

Examples: Grate ash 500 °CBed ash 850 °CBed ash 850 °C, 40 % of heat evaporating water

Red-hot ash boils off part of the water. Leave 0 for a quench where all the heat warms the water; 0.3–0.6 is plausible for ash above 500 °C.

Results

Above 100 °C some water flashes off on the ash; enter the evaporated share to see the vapour and make-up. Each kg evaporated removes about 27 times the heat of a kg warmed by 20 K.

Heat removed122.81kW
Quench water5.2800t/h
Water evaporated (lost as vapour, to make up)0t/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Grate ash 500 °C. The inputs, in the units selected above:

InputValue
Ash discharged1.2000 t/h
Ash temperature500.00 °C
Ash temperature after quench60.000 °C
Ash specific heat0.83736 kJ/(kg·K)
Quench water temperature rise20.000 K
Share of the heat taken by evaporating water0 %

Applying the formula below gives:

ResultValue
Heat removed122.81 kW
Quench water5.2800 t/h
Water evaporated (lost as vapour, to make up)0 t/h

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_a c_a (T_a - T_o)\)

\(\dot m_{ev} = \frac{f_{ev}\,\dot Q}{h_{fg}}, \quad \dot m_w = \frac{(1 - f_{ev})\,\dot Q}{c_w \Delta T_w} + \dot m_{ev}\)

Variables

Symbol Meaning SI unit
\(\dot m_a\) Ash discharged kg/s
\(T_a\) Ash temperature K
\(T_o\) Ash temperature after quench K
\(c_a\) Ash specific heat J/(kg·K)
\(\Delta T_w\) Quench water temperature rise K
\(\dot Q\) Heat removed W
\(\dot m_w\) Quench water kg/s
\(f_{ev}\) share of the heat taken by evaporating water -
\(\dot m_{ev}\) water evaporated, lost as vapour kg/s
\(h_{fg}\) latent heat of water at 101.325 kPa (IF97), about 2.257 MJ/kg
\(c_w\) specific heat of water, 4186.8 J/(kg·K)

Method and standards

Energy balance. Latent heat from FireCAD's IAPWS-IF97 at atmospheric pressure.

Where it is used

  • Ash handling design.

Common mistakes

  • Ash flow on fuel instead of discharged ash.

Assumptions and limits

  • With \(f_{ev} = 0\) (the default) all the heat warms the water and none evaporates. Ash above 100 °C flashes some water; the evaporated share is your estimate, and the heat to bring that water to 100 °C is neglected.
  • Ash specific heat is a constant 0.2 Btu/lb·°F; ASME PTC 4 gives a curve rising with temperature, so for bed ash at 800 °C and above the heat may be understated by some per cent.

References

  • Energy balance; residue specific heat 0.2 Btu/lb·°F (837 J/kg·K, owner-confirmed default)

Questions and answers

Why 0.2 Btu/lb·°F?

A conventional residue specific heat used in boiler heat balances; enter a measured value if you have one.

Where does the heat go?

Into the quench water, which is cooled or evaporates.

Biomass ash?

Light and often unburnt: check for smouldering before conveying.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.