Worked example
Example: 600 kg/h for 24 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Oil firing rate | 600.00 kg/h |
| Hours of storage | 24.000 h |
| Oil density at storage temperature | 950.00 kg/m³ |
| Ullage | 10.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Oil to hold | 15.158 m³ |
| Tank volume with ullage | 16.842 m³ |
Open this example in the calculator and change any input.
Formula
\(V_o = \frac{\dot m_o t}{\rho_o}, \quad V_t = \frac{V_o}{1 - u}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_o\) | Oil firing rate | kg/s |
| \(t\) | Hours of storage | s |
| \(\rho_o\) | Oil density at storage temperature | kg/m³ |
| \(u\) | Ullage | - |
| \(V_o\) | Oil to hold | m³ |
| \(V_t\) | Tank volume with ullage | m³ |
Method and standards
Definitions.
Where it is used
- Boiler house fuel oil system.
Common mistakes
- Density at 15 °C for heated oil.
Assumptions and limits
- Steady firing at the burner consumption. The unpumpable heel below the suction and any recirculation return are not added; increase the volume for them.
References
- V = ṁ t/ρ/(1 − u)
Questions and answers
How many hours?
Often 8–24 hours of firing at the oil burners' full rate.
Heavy oil?
Needs heating and a return line; size the heater with the tank.
Why ullage?
Thermal expansion and the overflow line.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.