Worked example
Example: Indian coal 12 t/h, 25 % excess air, sea level, 1 x 100 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon | 45.000 % |
| Hydrogen | 3.5000 % |
| Oxygen | 5.0000 % |
| Nitrogen | 1.0000 % |
| Sulphur | 0.50000 % |
| Ash | 35.000 % |
| Moisture | 10.000 % |
| Fuel firing rate at MCR | 12,000 kg/h |
| Excess air | 25.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Air temperature at the fan inlet | 35.000 °C |
| Flow margin | 20.000 % |
| Fans sharing the duty (1 = each fan 100 %) | 1.0000 - |
| Site pressure from | Altitude (ISO 2533 standard atmosphere) |
| Site altitude above sea level | 0 m |
| Barometric pressure at the site (absolute) | 1.0132 bar |
| Air heater, air side | 122.37 mmWC |
| Ducts, dampers and silencer | 61.183 mmWC |
| Burner, windbox or grate and bed | 152.96 mmWC |
| Pressure margin | 0 % |
| Fan efficiency | 80.000 % |
| Motor margin over the power absorbed | 10.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Design volume flow per fan (at the fan inlet) | 99,230 m³/h |
| Design fan pressure | 336.51 mmWC |
| Standard motor rating (IEC 60072-1 to 1000 kW, R20 series above) | 132.00 kW |
| Minimum motor rating (absorbed + margin) | 125.07 kW |
| Power absorbed at the design point | 113.70 kW |
| Design mass flow per fan (wet air) | 112,792 kg/h |
| Air density at the fan inlet | 1.1367 kg/m³ |
| Barometric pressure used | 1.0132 bar |
Open this example in the calculator and change any input.
Formula
\(\dot m = \dot m_f\,m_a\,(1+\omega)\,\frac{1 + m_Q}{n} \qquad \rho = \frac{(1+\omega)\,p}{\left(\frac{1}{M_{da}} + \frac{\omega}{M_w}\right) R\,T_a} \qquad \dot V = \frac{\dot m}{\rho}\)
\(\Delta p = (\Delta p_{ah} + \Delta p_d + \Delta p_b)(1 + m_p) \qquad P_s = \frac{\dot V\,\Delta p}{\eta_f} \qquad P_{m,min} = P_s\,(1 + m_m)\)
\(m_a\) is the dry air per kg of fuel from the exact-ratio combustion balance; \(P_{std}\) is the next IEC 60072-1 rating; \(p\) is the barometric pressure from ISO 2533 or entered.
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\), \(H\), \(O\), \(N\), \(S\) | carbon, hydrogen, oxygen, nitrogen, sulphur in the fuel as fired | – |
| \(A\) | ash | – |
| \(M\) | moisture | – |
| \(\dot m_f\) | fuel firing rate at MCR | kg/s |
| \(EA\) | excess air | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(T_a\) | air temperature at the fan inlet | K |
| \(m_Q\) | flow margin | – |
| \(n\) | fans sharing the duty | – |
| \(\text{site}\) | site pressure from altitude or entered | – |
| \(z\) | site altitude | m |
| \(p_s\) | barometric pressure entered | Pa |
| \(\Delta p_{ah}\) | air heater, air side | Pa |
| \(\Delta p_{d}\) | ducts, dampers and silencer | Pa |
| \(\Delta p_{b}\) | burner, windbox or grate and bed | Pa |
| \(m_p\) | pressure margin | – |
| \(\eta_f\) | fan efficiency | – |
| \(m_m\) | motor margin | – |
| \(\dot V\) | design volume flow per fan | m³/s |
| \(\Delta p\) | design fan pressure | Pa |
| \(P_{std}\) | standard motor rating | W |
| \(P_{m,min}\) | minimum motor rating | W |
| \(P_s\) | power absorbed | W |
| \(\dot m\) | design mass flow per fan | kg/s |
| \(\rho\) | air density at the fan inlet | kg/m³ |
| \(p\) | barometric pressure used | Pa |
| \(m_a\) | dry air per kg of fuel | kg/kg |
| \(M_{da}\), \(M_w\) | molar mass of dry air and water | kg/kmol |
| \(R\) | universal gas constant, 8314.46 (per kmol, to match \(M\) in kg/kmol) | J/(kmol·K) |
Method and standards
Combustion air from the exact-ratio balance with the ASME PTC 4-2013 air composition; humid-air density by the ideal-gas law; site pressure from ISO 2533; fan power as defined in ISO 5801; motor ratings from IEC 60072-1. Default efficiency and margins are FireCAD design practice (owner, 2026-11-10).
Where it is used
- Sizing forced draught fans for burners, grates and fluidised beds.
- Checking an FD fan for a fuel change or higher site temperature.
- Specifying fans for high-altitude sites.
Common mistakes
- Using standard air density at a hot or high-altitude site.
- Forgetting air heater leakage, which the FD fan must also supply.
- Taking the burner pressure only and missing the air heater, ducts and dampers.
Assumptions and limits
- Resistances at MCR flow; the pressure margin covers fouling and uncertainty if your specification asks for it.
- Air heater leakage to the gas side is not added to the FD fan flow; add it to the excess air if the air heater leaks significantly.
- Incompressible fan power; above about 5 kPa the true power is slightly lower (ISO 5801).
- The air is for complete combustion of all the fuel carbon (no unburnt-carbon deduction); the fan inlet static pressure is taken as the barometric pressure.
- The site altitude is used as the geopotential altitude of ISO 2533; the difference from height above sea level is negligible below 5000 m.
- Motor ratings follow IEC 60072-1 up to 1000 kW and an R20 preferred-number series above.
References
- ASME PTC 4-2013 (air composition)
- ISO 5801 (fan power)
- ISO 2533 (site pressure)
- IEC 60072-1 (motor ratings)
Questions and answers
How is an FD fan sized?
From the combustion air at MCR (fuel analysis and excess air), plus the flow margin, at the density of the hottest summer air at site. For 12 t/h of Indian coal at 25 % excess air and 35 °C the fan needs 27.6 m³/s; at 3.3 kPa and 80 % efficiency it absorbs 114 kW, so a 132 kW motor.
Which margins are applied?
The flow margin (default 20 %) and motor margin (default 10 %) are FireCAD design practice; a pressure margin is your input. All three are input boxes; your specification overrides them.
Why does altitude matter?
The fan moves volume. At altitude the air is thinner, so the same mass of combustion air needs more volume; at 450 m the volume is about 5 % larger than at sea level.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.