Safety Valve Reseat Pressure from Blowdown

Reseat (closing) pressure of a boiler safety valve from its set pressure and blowdown, and the margin to the working pressure so the valve closes tight.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileBoiler

Inputs

Examples: Set 10.5 bar g, 4 % blowdown, working 9.5 bar gSet 46 bar g, 3 %, working 43 bar gSet 7 bar g, 7 %, working 6.8 bar g (too close)

From the valve maker; the boiler code you follow limits it.

Results

The valve would not reseat above the working pressure: it will simmer or stay open. Lower the working pressure or reduce the blowdown.

Reseat pressure6.5100bar g
Reseat pressure minus working pressure-29.000kPa
Working pressure as a share of set pressure (gauge)97.143%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Set 10.5 bar g, 4 % blowdown, working 9.5 bar g. The inputs, in the units selected above:

InputValue
Set pressure10.500 bar g
Blowdown, share of set pressure4.0000 %
Normal working pressure9.5000 bar g

Applying the formula below gives:

ResultValue
Reseat pressure10.080 bar g
Reseat pressure minus working pressure58.000 kPa
Working pressure as a share of set pressure (gauge)90.476 %

Open this example in the calculator and change any input.

Formula

\(p_r = p_s\,(1 - b) \qquad \Delta p = p_r - p_w \qquad \frac{p_w}{p_s} \quad \text{(gauge pressures)}\)

Variables

Symbol Meaning SI unit
\(p_s\) set pressure (gauge) Pa
\(b\) blowdown, share of set pressure –
\(p_w\) normal working pressure (gauge) Pa
\(p_r\) reseat pressure (gauge) Pa
\(\Delta p\) reseat minus working pressure Pa
\(p_w/p_s\) working pressure as a share of set pressure –

Method and standards

Blowdown is the difference between set and reseat pressure as a share of set pressure, on gauge pressure. The calculator does not size the valve; that is a code calculation.

Where it is used

  • Setting safety valves after overhaul.
  • Choosing the working pressure margin of a boiler.
  • Investigating simmering or leaking valves.

Common mistakes

  • Mixing gauge and absolute pressures.
  • Running the boiler so close to set pressure that the valve never reseats.
  • Changing the blowdown ring without the maker's procedure.

Assumptions and limits

  • Blowdown as stated by the valve maker; no accumulation or backpressure effects.

References

  • Definition of blowdown as a share of set pressure (gauge)

Questions and answers

How do I find a safety valve's reseat pressure?

Set pressure less the blowdown. A valve set at 10.5 bar g with 4 % blowdown reseats at 10.08 bar g; with the boiler working at 9.5 bar g it closes with 0.58 bar to spare.

Why must the working pressure stay below the reseat pressure?

If the boiler runs above the reseat pressure, a valve that lifts will not close again until the pressure falls, wasting steam and wearing the seat; close to it the valve simmers and leaks.

What blowdown should the valve have?

The valve maker sets it with the adjusting ring, within the limits of the boiler code you follow. This page takes it as an input.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.