Electric (Electrode) Boiler kW and Current

Electrical power and three-phase line current an electric resistance or electrode steam boiler needs for a steam output, from the steam conditions (IAPWS-IF97).

Process steam and utilitiesChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)Boiler

Inputs

Examples: 2 t/h at 10.5 bar(a) saturated, feed 80 °C, 415 VElectrode boiler 10 t/h at 18 bar(a), feed 105 °C, 11 kV500 kg/h at 8 bar(a), feed 60 °C, 415 V, pf 0.98

Results

Blowdown is not included: electrode boilers control conductivity by blowdown, which takes heat too; add it to the steam output if it is significant.

Electrical power1,385.0kW
Line current (three-phase)1,926.9A
Heat to the steam1,357.3kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 t/h at 10.5 bar(a) saturated, feed 80 °C, 415 V. The inputs, in the units selected above:

InputValue
Steam output2,000.0 kg/h
Steam pressure (absolute)10.500 bar
Steam conditionDry saturated
Superheated steam temperature250.00 °C
Feedwater temperature80.000 °C
Boiler efficiency (heat loss from the shell)98.000 %
Supply line voltage415.00 V
Power factor100.00 %

Applying the formula below gives:

ResultValue
Electrical power1,385.0 kW
Line current (three-phase)1,926.9 A
Heat to the steam1,357.3 kW

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_s (h_s - h_{fw}) \qquad P = \frac{\dot Q}{\eta} \qquad I = \frac{P}{\sqrt{3}\,V\cos\varphi}\)

Variables

Symbol Meaning SI unit
\(\dot m_s\) steam output kg/s
\(p\) steam pressure Pa
\(\text{state}\) saturated or superheated –
\(T_s\) steam temperature K
\(T_{fw}\) feedwater temperature K
\(\eta\) boiler efficiency –
\(V\) line voltage V
\(\cos\varphi\) power factor –
\(P\) electrical power W
\(I\) line current A
\(\dot Q\) heat to steam W
\(h_s, h_{fw}\) enthalpies (IF97) J/kg

Method and standards

Steam heat from FireCAD's IAPWS-IF97; three-phase balanced load.

Where it is used

  • Sizing electric boilers and their supply.
  • Comparing electric and fuel-fired steam cost.
  • Power-to-heat projects.

Common mistakes

  • Forgetting the feedwater temperature in the kW.
  • Using phase voltage for current.
  • Ignoring the supply's demand charge.

Assumptions and limits

  • Balanced three-phase load; steady output.
  • Blowdown heat is not included. Electrode boilers hold the water conductivity by blowdown, which carries saturated water away; add its share to the output if significant.

References

  • IAPWS R7-97 IF97
  • Three-phase power P = √3 V I cos φ

Questions and answers

How many kW does an electric boiler need?

2 t/h of saturated steam at 10.5 bar(a) from 80 °C feedwater takes 1.36 MW of heat; at 98 % efficiency the boiler draws 1385 kW, 1930 A at 415 V.

Why use electrode boilers?

At medium voltage they reach tens of MW with no combustion, no stack and very fast response; they suit cheap or renewable power.

Is efficiency really 98 %?

Almost all the power becomes heat; the loss is the shell's heat to the room.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.