Boiler Efficiency at Low Fire (Burner Turndown)

Boiler efficiency at low fire from full-fire efficiency, the flue gas O₂ and temperature at both loads and the radiation loss, which rises as load falls.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileASME PTC 4 (fired steam generators)BoilerBurner and furnace

Inputs

Examples: Gas burner: 3 % O2 / 200 °C at full fire, 6 % / 150 °C at 25 %Oil burner: 3.5 % / 220 °C, 6.5 % / 170 °C at 35 %Coal-fired: 5 % / 170 °C, 8 % / 150 °C at 50 %

Ultimate analysis, as fired, by mass

Results

The radiation loss in kW is taken as the same at both loads, so its share rises as the load falls; burner purges and on–off cycling add more.

Excess air at full fire18.872%
Excess air at low fire42.325%
Sensible flue gas loss at full fire8.4917%
Sensible flue gas loss at low fire7.3280%
Radiation and unaccounted loss at low fire3.4286%
Boiler efficiency at low fire83.935%
Change from full fire (points)-1.0649%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Gas burner: 3 % O2 / 200 °C at full fire, 6 % / 150 °C at 25 %. The inputs, in the units selected above:

InputValue
Carbon74.868 %
Hydrogen25.132 %
Oxygen0 %
Nitrogen0 %
Sulphur0 %
Ash0 %
Moisture0 %
Air humidity (kg water per kg dry air)0.013000 kg/kg
Gross calorific value of the fuel, as fired55,500 kJ/kg
O₂ in dry flue gas at full fire3.0000 %
Flue gas temperature at full fire200.00 °C
O₂ in dry flue gas at low fire6.0000 %
Flue gas temperature at low fire150.00 °C
Combustion air temperature30.000 °C
Boiler efficiency at full fire (on GCV)84.000 %
Radiation and unaccounted loss at full fire1.0000 %
Low fire as a share of full fire25.000 %

Applying the formula below gives:

ResultValue
Excess air at full fire14.962 %
Excess air at low fire35.930 %
Sensible flue gas loss at full fire7.2358 %
Sensible flue gas loss at low fire5.8901 %
Radiation and unaccounted loss at low fire4.0000 %
Boiler efficiency at low fire82.346 %
Change from full fire (points)-1.6543 %

Open this example in the calculator and change any input.

Formula

\(L_g = \frac{\dot m_g\,[h_g(T_g) - h_g(T_a)]}{GCV}\)

\(L_{r2} = L_{r1} / x\)

\(\eta_2 = \eta_1 + (L_{g1} - L_{g2}) + (L_{r1} - L_{r2})\)

Variables

Symbol Meaning SI unit
\(C, H, O, N, S, A, M\) ultimate analysis of the fuel, as fired -
\(\omega\) air humidity kg/kg
\(GCV\) gross calorific value, as fired J/kg
\(O_{2,1}\) dry flue gas O₂ at full fire -
\(O_{2,2}\) dry flue gas O₂ at low fire -
\(T_{g1}\) flue gas temperature at full fire K
\(T_{g2}\) flue gas temperature at low fire K
\(T_a\) combustion air temperature K
\(T_g\) flue gas temperature K
\(\eta_1\) efficiency at full fire -
\(\eta_2\) efficiency at low fire -
\(\Delta\eta\) change from full fire -
\(L_{r1}\) radiation and unaccounted loss at full fire -
\(L_{r2}\) radiation and unaccounted loss at low fire -
\(x\) low fire as a share of full fire -
\(EA_1\) excess air at full fire -
\(EA_2\) excess air at low fire -
\(L_{g1}\) stack loss at full fire -
\(L_{g2}\) stack loss at low fire -
\(L_g\) stack loss -
\(\dot m_g\) wet flue gas per kg fuel kg/kg
\(h_g\) flue gas enthalpy J/kg

Method and standards

Excess air at each load comes from the measured dry O₂ and the fuel analysis; the wet flue gas per kg fuel and its enthalpy rise from air to stack temperature (NIST Shomate data) give the stack loss at each load. The change in stack loss and the rise in radiation loss, constant in kW and so inversely proportional to load as a share, are applied to the full-fire efficiency.

Where it is used

  • Comparing burners by turndown ratio and low-fire O₂.
  • Explaining why a boiler running mostly at low fire uses more fuel per tonne of steam.
  • Deciding between one large and two smaller boilers.

Common mistakes

  • Quoting the full-fire efficiency for a boiler that runs mostly at low fire.
  • Ignoring purge and on–off cycling losses on boilers that cycle often.
  • Reading O₂ on a wet-basis analyser and entering it as dry.

Assumptions and limits

  • Steady firing at each load; purge and cycling losses are not included.
  • Radiation loss in kW is the same at both loads; the unaccounted part of the entered loss is scaled the same way.
  • Excess air from O₂ assumes complete combustion (no CO), which may not hold at low fire.
  • The flue gas losses shown are sensible heat only (dry gas and water vapour from the air to the stack temperature). The latent heat of the water from hydrogen and moisture is the same per kg of fuel at both loads, so it cancels in the efficiency change but is not part of the loss figures.
  • Unburnt losses are taken as unchanged.

References

  • Stack loss from the combustion balance (NIST Shomate gas properties)
  • ASME PTC 4 loss method

Questions and answers

How much efficiency does a gas boiler lose at 25 % load?

In the example, O₂ rising from 3 % to 6 % while the stack cools from 200 °C to 150 °C cuts the stack loss, but the radiation loss grows from 1 % to 4 %, so efficiency falls about 1.7 points.

Why does radiation loss rise at low fire?

The casing loses about the same kW at any load, because it stays at much the same temperature, so as a share of a smaller firing rate it grows inversely with load.

Why does O₂ rise at low fire?

Most burners need more excess air at low fire to keep mixing and flame stability; better burners and O₂ trim keep it lower.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.