Worked example
Example: Gas burner: 3 % O2 / 200 °C at full fire, 6 % / 150 °C at 25 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon | 74.868 % |
| Hydrogen | 25.132 % |
| Oxygen | 0 % |
| Nitrogen | 0 % |
| Sulphur | 0 % |
| Ash | 0 % |
| Moisture | 0 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Gross calorific value of the fuel, as fired | 55,500 kJ/kg |
| O₂ in dry flue gas at full fire | 3.0000 % |
| Flue gas temperature at full fire | 200.00 °C |
| O₂ in dry flue gas at low fire | 6.0000 % |
| Flue gas temperature at low fire | 150.00 °C |
| Combustion air temperature | 30.000 °C |
| Boiler efficiency at full fire (on GCV) | 84.000 % |
| Radiation and unaccounted loss at full fire | 1.0000 % |
| Low fire as a share of full fire | 25.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Excess air at full fire | 14.962 % |
| Excess air at low fire | 35.930 % |
| Sensible flue gas loss at full fire | 7.2358 % |
| Sensible flue gas loss at low fire | 5.8901 % |
| Radiation and unaccounted loss at low fire | 4.0000 % |
| Boiler efficiency at low fire | 82.346 % |
| Change from full fire (points) | -1.6543 % |
Open this example in the calculator and change any input.
Formula
\(L_g = \frac{\dot m_g\,[h_g(T_g) - h_g(T_a)]}{GCV}\)
\(L_{r2} = L_{r1} / x\)
\(\eta_2 = \eta_1 + (L_{g1} - L_{g2}) + (L_{r1} - L_{r2})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C, H, O, N, S, A, M\) | ultimate analysis of the fuel, as fired | - |
| \(\omega\) | air humidity | kg/kg |
| \(GCV\) | gross calorific value, as fired | J/kg |
| \(O_{2,1}\) | dry flue gas O₂ at full fire | - |
| \(O_{2,2}\) | dry flue gas O₂ at low fire | - |
| \(T_{g1}\) | flue gas temperature at full fire | K |
| \(T_{g2}\) | flue gas temperature at low fire | K |
| \(T_a\) | combustion air temperature | K |
| \(T_g\) | flue gas temperature | K |
| \(\eta_1\) | efficiency at full fire | - |
| \(\eta_2\) | efficiency at low fire | - |
| \(\Delta\eta\) | change from full fire | - |
| \(L_{r1}\) | radiation and unaccounted loss at full fire | - |
| \(L_{r2}\) | radiation and unaccounted loss at low fire | - |
| \(x\) | low fire as a share of full fire | - |
| \(EA_1\) | excess air at full fire | - |
| \(EA_2\) | excess air at low fire | - |
| \(L_{g1}\) | stack loss at full fire | - |
| \(L_{g2}\) | stack loss at low fire | - |
| \(L_g\) | stack loss | - |
| \(\dot m_g\) | wet flue gas per kg fuel | kg/kg |
| \(h_g\) | flue gas enthalpy | J/kg |
Method and standards
Excess air at each load comes from the measured dry O₂ and the fuel analysis; the wet flue gas per kg fuel and its enthalpy rise from air to stack temperature (NIST Shomate data) give the stack loss at each load. The change in stack loss and the rise in radiation loss, constant in kW and so inversely proportional to load as a share, are applied to the full-fire efficiency.
Where it is used
- Comparing burners by turndown ratio and low-fire O₂.
- Explaining why a boiler running mostly at low fire uses more fuel per tonne of steam.
- Deciding between one large and two smaller boilers.
Common mistakes
- Quoting the full-fire efficiency for a boiler that runs mostly at low fire.
- Ignoring purge and on–off cycling losses on boilers that cycle often.
- Reading O₂ on a wet-basis analyser and entering it as dry.
Assumptions and limits
- Steady firing at each load; purge and cycling losses are not included.
- Radiation loss in kW is the same at both loads; the unaccounted part of the entered loss is scaled the same way.
- Excess air from O₂ assumes complete combustion (no CO), which may not hold at low fire.
- The flue gas losses shown are sensible heat only (dry gas and water vapour from the air to the stack temperature). The latent heat of the water from hydrogen and moisture is the same per kg of fuel at both loads, so it cancels in the efficiency change but is not part of the loss figures.
- Unburnt losses are taken as unchanged.
References
- Stack loss from the combustion balance (NIST Shomate gas properties)
- ASME PTC 4 loss method
Questions and answers
How much efficiency does a gas boiler lose at 25 % load?
In the example, O₂ rising from 3 % to 6 % while the stack cools from 200 °C to 150 °C cuts the stack loss, but the radiation loss grows from 1 % to 4 %, so efficiency falls about 1.7 points.
Why does radiation loss rise at low fire?
The casing loses about the same kW at any load, because it stays at much the same temperature, so as a share of a smaller firing rate it grows inversely with load.
Why does O₂ rise at low fire?
Most burners need more excess air at low fire to keep mixing and flame stability; better burners and O₂ trim keep it lower.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.