Boiler Purge and On-Off Cycling Heat Loss

Heat carried away by the purge air at each burner start of an on–off boiler, and the yearly heat, fuel and cost lost to purging from the number of starts.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileASME PTC 4 (fired steam generators)BoilerBurner and furnace

Inputs

Examples: 8 000 Nm³/h purge, 60 s, 200 °C, 24 starts a day16 000 Nm³/h, 90 s, 220 °C, 48 starts, 300 days2 000 Nm³/h, 30 s, 180 °C, 12 starts, 350 days

Results

Dry air with NIST Shomate enthalpy. The leaving temperature falls during a long purge; use the mean you measure. Fewer starts (lower burner turndown limit, modulation) cut this loss.

Air mass per purge516.93kg
Heat lost per purge97,025kJ
Heat lost per year1,397.2GJ
Fuel heat per year to replace it1,624.6GJ
Fuel cost per year1,949,528

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 8 000 Nm³/h purge, 60 s, 200 °C, 24 starts a day. The inputs, in the units selected above:

InputValue
Purge air flow (normal: 0 °C, 101.325 kPa)8,000.0 Nm³/h
Purge time per start (pre-purge plus post-purge)60.000 s
Mean temperature of the air leaving the boiler during purge200.00 °C
Air temperature at the fan inlet30.000 °C
Burner starts per day24.000 -
Operating days per year330.00 -
Boiler efficiency (to turn the heat into fuel)88.000 %
Fuel cost per GJ of fuel heat (your currency)900.00 -

Applying the formula below gives:

ResultValue
Air mass per purge172.31 kg
Heat lost per purge29,671 kJ
Heat lost per year235.00 GJ
Fuel heat per year to replace it267.04 GJ
Fuel cost per year240,337

Open this example in the calculator and change any input.

Formula

\(m_a = \dot V_N\, \rho_N\, t_p\)

\(Q_p = m_a \int_{T_a}^{T_g} c_p\, dT\)

\(Q_y = Q_p\, n\, N_d, \quad Q_F = Q_y / \eta, \quad C_y = Q_F\, c_F\)

Variables

Symbol Meaning SI unit
\(\dot V_N\) Purge air flow at normal conditions (0 °C, 101.325 kPa) Nm³/s
\(t_p\) Purge time per start (pre-purge plus post-purge) s
\(T_g\) Mean temperature of the air leaving the boiler during purge K
\(T_a\) Air temperature at the fan inlet K
\(n\) Burner starts per day -
\(N_d\) Operating days per year -
\(\eta\) Boiler efficiency (to turn the heat into fuel) -
\(c_F\) Fuel cost per GJ of fuel heat (your currency) -
\(m_a\) Air mass per purge kg
\(Q_p\) Heat lost per purge J
\(Q_y\) Heat lost per year J
\(Q_F\) Fuel heat per year to replace it J
\(C_y\) Fuel cost per year -
\(\rho_N\) Density of dry air at normal conditions (0 °C, 101.325 kPa) kg/Nm³
\(c_p\) Specific heat of air J/(kg·K)

Method and standards

Each start draws a purge volume of fresh air through the furnace and passes, cooling the hot boiler. The heat is the air mass times its enthalpy rise from fan inlet to boiler outlet (NIST Shomate dry-air enthalpy). The yearly loss scales with starts per day and days in service; dividing by efficiency gives the fuel that replaces it. The purge flow and time are inputs: NFPA 85 and EN 746-2 set the purge (air changes before ignition) as applied by the burner maker; this calculator does not compute them.

Where it is used

  • Justifying a burner with wider turndown or modulating control.
  • Comparing one large boiler cycling with two smaller ones.
  • Estimating savings from boiler sequencing.

Common mistakes

  • Using the full-load stack temperature: during purge the outlet temperature falls.
  • Forgetting post-purge after each stop.
  • Counting only the purge: standby losses between firing also grow with cycling.

Assumptions and limits

  • Dry air, steady flow during purge. The flow is at normal conditions (0 °C, 101.325 kPa); a US standard flow at 60 °F is about 5.5 % less air for the same number.
  • Radiation and standby losses not included.

References

  • NFPA 85 / EN 746-2 purge requirement (air changes before ignition)
  • NIST Shomate air enthalpy (PTC 4 air composition)

Questions and answers

How much heat does one purge take away?

8 000 Nm³/h of air for 60 s is about 172 kg of air; heated from 30 °C to 200 °C it carries 29.7 MJ out of the boiler.

Is that significant over a year?

At 24 starts a day for 330 days it is 235 GJ of heat, or 267 GJ of fuel at 88 % efficiency, which costs about 240 000 at 900 per GJ.

How do I cut cycling losses?

Reduce the number of starts: a burner with wider turndown, modulating control, a properly sized boiler or sequencing of several boilers so one runs at low fire instead of cycling.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.