Boiler Feed Pump Sizing (Flow, Head, Motor)

Design flow, total head, power and motor of a boiler feed water pump from the boiler MCR, drum pressure, pressure drops and deaerator conditions.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)Hydraulic Institute (pumps)BoilerDeaerator and feedwater systemPump

Inputs

Examples: 50 t/h, drum 70 bar(a), deaerator 1.2 bar(a), 2 x 100 %120 t/h, drum 110 bar(a), deaerator 6 bar(a), head margin 5 %20 t/h shell boiler 17.5 bar(a), 2 x 50 %

Flow

20 % covers peak load (110 % of rating) and wear. Default from FireCAD design practice; enter your specification's value.

Discharge

Usually the highest safety-valve set pressure on the drum, so the pump can feed the boiler while the valves lift. Absolute; choose a gauge unit to enter gauge readings.

Suction

Pump and motor

Enter your specification's head margin, if any; the flow margin above already raises the duty.
From the pump maker's curve at the duty point. 68 % is a typical maker's value for this size; some makers offer better. Default from FireCAD design practice; enter your specification's value.
18 % for pump motors. Default from FireCAD design practice; enter your specification's value.

Results

Design flow per pump160.86m³/h
Design total head1,377.2m
Standard motor rating (IEC 60072-1)900.00kW
Minimum motor rating (absorbed + margin)862.73kW
Power absorbed at the design point731.13kW
Design mass flow per pump146,160kg/h
Pump discharge pressure (absolute)130.41bar
Pump suction pressure (absolute)7.6929bar
Feedwater density at deaerator saturation908.59kg/m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 50 t/h, drum 70 bar(a), deaerator 1.2 bar(a), 2 x 100 %. The inputs, in the units selected above:

InputValue
Boiler steam output at MCR50,000 kg/h
Blowdown, as a share of steam2.0000 %
Flow margin20.000 %
Pumps sharing the duty (1 = each pump 100 %)1.0000 -
Drum pressure for pump sizing (absolute)70.000 bar
Economiser pressure drop200.00 kPa
Feed control valve pressure drop400.00 kPa
Discharge piping, fittings and check-valve losses150.00 kPa
Drum water level above the pump centreline25.000 m
Deaerator pressure (absolute)1.2000 bar
Deaerator water level above the pump centreline12.000 m
Suction line friction loss0.60000 m
Head margin0 %
Pump efficiency68.000 %
Motor margin over the power absorbed18.000 %

Applying the formula below gives:

ResultValue
Design flow per pump64.093 m³/h
Design total head828.42 m
Standard motor rating (IEC 60072-1)250.00 kW
Minimum motor rating (absorbed + margin)239.66 kW
Power absorbed at the design point203.10 kW
Design mass flow per pump61,200 kg/h
Pump discharge pressure (absolute)79.841 bar
Pump suction pressure (absolute)2.2675 bar
Feedwater density at deaerator saturation954.87 kg/m³

Open this example in the calculator and change any input.

Formula

\(\dot m = \frac{\dot m_{MCR}\,(1 + b)\,(1 + m_Q)}{n} \qquad Q = \frac{\dot m}{\rho}\)

\(p_1 = p_{da} + \rho g\,(z_{da} - h_{fs}) \qquad p_{req} = p_{dr} + \Delta p_{eco} + \Delta p_v + \Delta p_l + \rho g\,z_{dr}\)

\(H = \frac{p_{req} - p_1}{\rho g}\,(1 + m_H) \qquad p_2 = p_1 + \rho g H \qquad P_s = \frac{\dot m\,g\,H}{\eta_p} \qquad P_{m,min} = P_s\,(1 + m_m)\)

\(P_{std}\) is the next IEC 60072-1 standard rating at or above \(P_{m,min}\).

Variables

Symbol Meaning SI unit
\(\dot m_{MCR}\) boiler steam output at MCR kg/s
\(b\) blowdown as a share of steam –
\(m_Q\) flow margin –
\(n\) pumps sharing the duty –
\(p_{dr}\) drum pressure for sizing, absolute Pa
\(\Delta p_{eco}\) economiser pressure drop Pa
\(\Delta p_{v}\) feed control valve pressure drop Pa
\(\Delta p_{l}\) discharge piping and fitting losses Pa
\(z_{dr}\) drum level above the pump centreline m
\(p_{da}\) deaerator pressure, absolute Pa
\(z_{da}\) deaerator water level above the pump centreline m
\(h_{fs}\) suction line friction loss m
\(m_H\) head margin –
\(\eta_p\) pump efficiency –
\(m_m\) motor margin –
\(Q\) design flow per pump m³/s
\(H\) design total head m
\(P_{std}\) standard motor rating W
\(P_{m,min}\) minimum motor rating W
\(P_s\) power absorbed W
\(\dot m\) design mass flow per pump kg/s
\(p_2\) pump discharge pressure Pa
\(p_1\) pump suction pressure Pa
\(\rho\) feedwater density, saturated at the deaerator pressure kg/m³
\(p_{req}\) pressure needed at the pump discharge Pa
\(g\) standard gravity, 9.806 65 m/s²

Method and standards

Pressure balance from the deaerator to the drum, with head and power as defined in ANSI/HI 1.6. Feedwater density from FireCAD's IAPWS-IF97 for saturated water at the deaerator pressure. Motor ratings from the IEC 60072-1 series. Default efficiency, margins and flow allowance are FireCAD design practice (owner, 2026-11-10); all are inputs.

Where it is used

  • Specifying boiler feed pumps for drum, once-through and shell boilers.
  • Checking an existing pump for a boiler uprating or a change in pressure.
  • Motor selection for feed pumps.

Common mistakes

  • Taking the drum pressure as the pump head and forgetting the economiser, control valve and line losses.
  • Adding flow margin twice: once on the steam flow and again on the pump.
  • Forgetting recirculation (minimum flow) and blowdown flow in the pump capacity.

Assumptions and limits

  • Feedwater saturated at the deaerator pressure; the density change through the pump is neglected.
  • The discharge pressure drops are at the design flow; enter them at that flow.
  • Minimum-flow recirculation, balancing-device leak-off and attemperator spray taken from the pump discharge add to the flow: include them in the margin or the MCR.
  • Check NPSH separately with the deaerator elevation calculator.

References

  • ANSI/HI 1.6 (head and power definitions)
  • IAPWS R7-97(2012) IF97 (feedwater density)
  • IEC 60072-1 (motor ratings)

Questions and answers

How is a boiler feed pump sized?

Flow = MCR × (1 + blowdown) × (1 + flow margin), divided among the pumps sharing the duty. The discharge must reach the drum at its highest safety-valve set pressure plus the economiser, control valve and line losses and the static height. For a 50 t/h boiler at 70 bar(a) this gives 64 m³/h at 828 m head, 203 kW absorbed at 68 % and a 250 kW motor.

Why the safety-valve set pressure?

The pump must keep feeding the boiler while the safety valves lift, so the drum pressure for sizing is usually the highest set pressure. Use the value your specification or boiler code requires.

Where do the 20 % flow margin and 18 % motor margin come from?

They are FireCAD design-practice defaults (peak load is about 110 % of rating, plus wear). Every margin is an input; your specification overrides them.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.