Worked example
Example: Shell boiler 10 t/h, feed 150 ppm, limit 3 000 ppm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steam generated | 10,000 kg/h |
| Dissolved solids in feedwater | 150.00 ppm |
| Maximum dissolved solids in boiler water | 3,000.0 ppm |
| Drum pressure (absolute) | 10.500 bar |
| Feedwater temperature | 105.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Blowdown flow | 526.32 kg/h |
| Blowdown as a share of steam | 5.2632 % |
| Blowdown as a share of feedwater | 5.0000 % |
| Feedwater flow | 10,526 kg/h |
| Cycles of concentration | 20.000 |
| Heat leaving with the blowdown (above feedwater) | 48.422 kW |
| Boiler water enthalpy (saturated liquid) | 772.10 kJ/kg |
| Feedwater enthalpy | 440.90 kJ/kg |
Open this example in the calculator and change any input.
Formula
Dissolved solids enter only with the feedwater and leave only with the blowdown (steam carries none):
\(F\,c_{fw} = B\,c_{bd} \qquad F = S + B \quad\Rightarrow\quad B = \frac{S\,c_{fw}}{c_{bd} - c_{fw}}\)
\(N = \frac{c_{bd}}{c_{fw}} \qquad B/F = \frac{c_{fw}}{c_{bd}} \qquad \dot Q_{bd} = B\,(h_f - h_{fw})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | steam generated | kg/s |
| \(c_{fw}\) | dissolved solids in feedwater (mass fraction) | – |
| \(c_{bd}\) | maximum dissolved solids in boiler water | – |
| \(p\) | drum absolute pressure | Pa |
| \(T_{fw}\) | feedwater temperature | K |
| \(B\) | blowdown flow | kg/s |
| \(B/S\) | blowdown as a share of steam | – |
| \(B/F\) | blowdown as a share of feedwater | – |
| \(F\) | feedwater flow | kg/s |
| \(N\) | cycles of concentration | – |
| \(\dot Q_{bd}\) | heat leaving with the blowdown, above feedwater | W |
| \(h_{f}\) | saturated liquid enthalpy at drum pressure | J/kg |
| \(h_{fw}\) | feedwater enthalpy | J/kg |
Method and standards
Steady-state mass balance on dissolved solids, the standard basis for continuous blowdown control. Enthalpies from FireCAD's IAPWS-IF97 implementation. Boiler-water limits are the user's input, taken from the boiler maker or a recognised water-chemistry guideline for the drum pressure.
Where it is used
- Setting continuous blowdown of drum boilers from feedwater and boiler water TDS or silica.
- Water treatment design: what make-up quality allows what blowdown.
- Make-up water and chemical consumption estimates.
Common mistakes
- Using conductivity limits from one boiler pressure for another; the limits fall as pressure rises.
- Expressing blowdown as a share of steam in one place and of feedwater in another.
- Forgetting that returned condensate lowers the feedwater TDS.
Assumptions and limits
- Steady state; no solids carried over with the steam and none removed by intermittent (bottom) blowdown. At high drum pressure silica volatilises into the steam, so for silica the balance overstates the blowdown needed; use the boiler maker's silica curve.
- A warning appears when the blowdown exceeds 10 % of the steam.
- Concentrations by mass (ppm = mg/kg); for dilute water mg/L is the same number.
- Feedwater enthalpy at drum pressure.
References
- IAPWS R7-97(2012) IF97
- boiler-water limits from the boiler maker or a water-chemistry guideline (user input)
Questions and answers
How is blowdown calculated?
By a dissolved-solids balance. Solids enter with the feedwater and leave only with the blowdown, so B = S·c_fw/(c_bd − c_fw). For 10 t/h with 150 ppm feed and a 3 000 ppm limit, B = 526 kg/h, 5.3 % of the steam.
Where do the boiler-water limits come from?
From the boiler maker or a water-chemistry guideline for the drum pressure and the controlling species (TDS, silica, alkalinity, chloride). Use the species that gives the highest blowdown.
Why does the heat loss matter?
Blowdown leaves as saturated water at drum pressure. For a 50 t/h boiler at 45 bar(a) blowing down 3.4 % of steam, about 254 kW leaves above the feedwater enthalpy; a flash vessel and cooler can recover most of it.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.