Worked example
Example: Wood chips dried from 45 % to 30 % moisture. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gross calorific value on dry basis | 18,500 kJ/kg |
| Fuel moisture now, as fired | 45.000 % |
| Boiler efficiency now (on GCV) | 70.000 % |
| Fuel moisture after the change | 30.000 % |
| Flue gas temperature at the boiler exit | 180.00 °C |
| Reference (air and fuel) temperature | 30.000 °C |
| Fuel firing rate now | 10.000 t/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| GCV as fired now | 10,175 kJ/kg |
| GCV as fired after the change | 12,950 kJ/kg |
| Fuel moisture loss now | 12.008 % |
| Fuel moisture loss after the change | 6.2901 % |
| Boiler efficiency after the change | 75.718 % |
| Change in efficiency (points) | 5.7183 % |
| Fuel rate for the same steam output | 7.2638 t/h |
Open this example in the calculator and change any input.
Formula
\(GCV_{ar} = GCV_d (1 - M)\)
\(L_M = \frac{M\,[h_v(T_g, 1\ \text{psia}) - h_f(T_a)]}{GCV_{ar}}\)
\(\eta_2 = \eta_1 + L_{M1} - L_{M2}\)
\(\dot m_{f2} = \dot m_{f1} \frac{GCV_1\, \eta_1}{GCV_2\, \eta_2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(GCV_d\) | gross calorific value on dry basis | J/kg |
| \(GCV_1\) | GCV as fired now | J/kg |
| \(GCV_2\) | GCV as fired after the change | J/kg |
| \(GCV_{ar}\) | GCV as fired at moisture M | J/kg |
| \(M_1\) | fuel moisture now, as fired | - |
| \(M_2\) | fuel moisture after the change | - |
| \(M\) | fuel moisture, as fired | - |
| \(\eta_1\) | boiler efficiency now (GCV basis) | - |
| \(\eta_2\) | efficiency after the change | - |
| \(\Delta\eta\) | change in efficiency | - |
| \(T_g\) | flue gas temperature at the boiler exit | K |
| \(T_a\) | reference (air and fuel) temperature | K |
| \(L_{M1}\) | fuel moisture loss now | - |
| \(L_{M2}\) | fuel moisture loss after the change | - |
| \(L_M\) | fuel moisture loss | - |
| \(h_v\) | enthalpy of water vapour at T_g and 1 psia | J/kg |
| \(h_f\) | enthalpy of saturated liquid water at T_a | J/kg |
| \(\dot m_{f1}\) | fuel firing rate now | kg/s |
| \(\dot m_{f2}\) | fuel rate for the same steam output | kg/s |
Method and standards
The fuel moisture loss follows ASME PTC 4: the water enters as liquid at the reference temperature and leaves as vapour at the flue gas temperature, with the vapour enthalpy taken at 1 psia from IAPWS-IF97. The other losses are a fixed amount per kg of dry fuel, so they keep the same share of the fuel's heat at any moisture; the efficiency therefore changes by exactly the change in the moisture loss.
Where it is used
- Judging whether a fuel dryer or covered fuel storage pays.
- Explaining a drop in efficiency in the monsoon.
- Setting moisture limits in a biomass or coal purchase contract.
Common mistakes
- Comparing efficiencies on GCV and NCV bases as if they were the same.
- Using the dry-basis GCV as the as-fired value.
- Forgetting that a wetter fuel also needs more tonnes per hour through the feeders.
Assumptions and limits
- Other losses are held at a fixed share of the fuel heat; the extra flue gas mass, any change in air demand and fan power from the added moisture are not included.
- The liquid reference is your reference temperature \(T_a\), not PTC 4's fixed 25 °C; it is consistent with the efficiency entered only if that efficiency used the same reference.
- Flue gas temperature is taken as unchanged by the moisture change.
- Moisture is total moisture, as fired.
References
- ASME PTC 4-2013 fuel moisture loss (water vapour at 1 psia)
- IAPWS-IF97
Questions and answers
How much does drying wood chips from 45 % to 30 % moisture gain?
With a dry GCV of 18.5 MJ/kg, 180 °C stack and 70 % efficiency now, efficiency rises about 5.7 points to 75.7 %, and fuel by weight falls from 10 to 7.3 t/h for the same steam.
Why does moisture cost so much?
Every kg of water in the fuel must be evaporated and leaves the stack as vapour, taking about 2.6 MJ with it, while the as-fired GCV falls in proportion to the dry matter.
Does the method change the other losses?
No. Dry gas, unburnt carbon and radiation losses are held at the same share of the fuel's heat; extra moisture also adds a little flue gas and fan power, which is not included.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.