Worked example
Example: Same pack, co-current at 75 deg. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow pattern | Co-current (downflow) |
| Plate length in the flow direction | 2.0000 m |
| Perpendicular spacing between plates | 50.000 mm |
| Plate angle from horizontal | 75.000 ° |
| Flow to the plate pack | 360.00 m³/h |
| Plate width | 2.0000 m |
| Number of plate channels | 50.000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mean fluid velocity between the plates | 20.000 mm/s |
| Critical settling to fluid velocity ratio | 0.10653 |
| Critical settling velocity (smallest fully removed) | 7.6703 m/h |
| Projected (horizontal) plate area | 51.764 m² |
| Loading on the projected area | 6.9547 m/h |
Open this example in the calculator and change any input.
Formula
\(\frac{v_s}{v_f} = \frac{d}{L_p\cos\theta + d\sin\theta}\ \text{(counter-current)}, \quad \frac{d}{L_p\cos\theta - d\sin\theta}\ \text{(co-current)}, \quad \frac{d}{L_p\cos\theta}\ \text{(cross-flow)}\)
\(v_f = \frac{Q}{nwd}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{flow}\) | Flow pattern | - |
| \(L_p\) | Plate length in the flow direction | m |
| \(d\) | Perpendicular spacing between plates | m |
| \(\theta\) | Plate angle from horizontal | rad |
| \(Q\) | Flow to the plate pack | m³/s |
| \(w\) | Plate width | m |
| \(n\) | Number of plate channels | - |
| \(v_f\) | Mean fluid velocity between the plates | m/s |
| \(v_s/v_f\) | Critical settling to fluid velocity ratio | - |
| \(v_s\) | Critical settling velocity (smallest fully removed) | m/s |
| \(A_p\) | Projected (horizontal) plate area | m² |
| \(Q/A_p\) | Loading on the projected area | m/s |
Method and standards
Ideal-settling trajectory analysis between parallel inclined plates.
Where it is used
- Retrofitting sedimentation basins with plate packs.
- Comparing plate spacing and angle.
Common mistakes
- Using the tank footprint as the settling area.
- Ignoring flow maldistribution between channels.
Assumptions and limits
- Laminar, uniform flow; discrete particles.
Questions and answers
Which flow pattern is best?
Below about 60° the three are nearly equal; above 60° counter-current removes the slowest-settling particles.
How do plates raise capacity?
Each plate adds settling area: the projected area of all plates, not the tank footprint, sets the critical settling velocity.
What do the defaults represent?
An illustrative case: Same pack, co-current at 75 deg. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 10-7, eqs. 10-36, 10-40 and 10-42 and Example 10-7