Worked example
Example: Illustrative: 60 Nm3/h at 10 % ozone, 0.5 m3/s water, 95 % transfer, 0.1 ppmv limit. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Feed gas flow (normal) | 60.000 Nm³/h |
| Ozone in the feed gas, by volume | 10.000 % |
| Water flow | 1,800.0 m³/h |
| Transfer efficiency | 95.000 % |
| Vent limit for ozone, ppmv | 0.10000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Ozone generated | 12.849 kg/h |
| Applied ozone dose | 7.1381 mg/L |
| Transferred ozone dose | 6.7812 mg/L |
| Off-gas ozone, ppmv | 5,524.9 |
| Off-gas ozone, mass per normal volume | 11.831 g/m³ |
| Destruct efficiency for the vent limit | 99.998 % |
Open this example in the calculator and change any input.
Formula
\(\dot m_{O_3} = \frac{Q_g\,y_{O_3}}{V_m}M_{O_3}, \quad D_{applied} = \frac{\dot m_{O_3}}{Q_w}, \quad D_{transferred} = TE\cdot D_{applied}\)
\(C_{off} = \frac{y_{O_3}(1 - TE)}{1 - y_{O_3}TE}, \quad \eta_{destruct} = 1 - \frac{C_{vent}}{C_{off}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_g\) | Feed gas flow (normal) | Nm³/s |
| \(y_{O_3}\) | Ozone in the feed gas, by volume | - |
| \(Q_w\) | Water flow | m³/s |
| \(TE\) | Transfer efficiency | - |
| \(C_{vent}\) | Vent limit for ozone, ppmv | - |
| \(\dot m_{O_3}\) | Ozone generated | kg/s |
| \(D_{applied}\) | Applied ozone dose | kg/m³ |
| \(D_{transferred}\) | Transferred ozone dose | kg/m³ |
| \(C_{off}\) | Off-gas ozone, ppmv | - |
| \(\eta_{destruct}\) | Destruct efficiency for the vent limit | - |
Method and standards
Gas-phase mass balance on an ozone contactor.
Where it is used
- Ozone dose and generator sizing.
- Off-gas destruct specification.
Common mistakes
- Confusing weight and volume per cent of ozone.
- Taking applied dose as transferred dose.
Assumptions and limits
- Steady state; normal gas volumes.
References
- Ozone mass balance between feed gas
- water and off-gas
Questions and answers
Why destroy the off-gas?
Even at 99.5 % transfer, a feed of several per cent ozone leaves hundreds of ppmv in the off-gas, three to four orders above occupational limits.
What transfer efficiency is typical?
Fine-bubble diffuser contactors reach 85–95 %; side-stream injection with degassing can exceed 95 %.
What do the defaults represent?
An illustrative oxygen-fed plant: 60 Nm³/h of gas at 10 % ozone by volume into 0.5 m³/s of water with 95 % transfer and a 0.1 ppmv vent limit.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 13-7, Example 13-9