FireCADCalc

Ozonation: Direct and Hydroxyl Radical Destruction of a Micropollutant

Share of target destruction by hydroxyl radicals during ozonation (R_ct concept), half-life and time for a given removal with first-order ozone decay.

Inputs

Examples: Geosmin with Rct 1e-8Atrazine (kO3 6, kHO 3e9), 2 mg/L ozone, decay 0.2/min, Rct 1e-7, 50 % removal

Accepted: 100,000 to 2E+10
Accepted: 0 to 1E+9
Accepted: 1E-12 to 1E-5
Accepted: 0.01 to 50 mg/L
Accepted: 6E-5 to 60 1/min
Accepted: 1 to 99.999 %

Results

[O₃] = [O₃]₀e^(−kt) and ln(R₀/R) = ([O₃]₀/k)(k_HO•R_ct + k_O₃)(1 − e^(−kt)) for a batch reactor or ideal plug flow. R_ct is typically 10⁻¹⁰ to 10⁻⁷ in natural waters (Elovitz and von Gunten).

Share of destruction by hydroxyl radicals98.039%
Effective rate constant, L/(mol·s)306.00
Initial ozone, mol/L4.1668e-05
Largest removal possible before the ozone is gone (as ln)3.8252
Half-life of the target0.99962min
Time for the target removal0.99962min

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Geosmin with Rct 1e-8. The inputs, in the units selected above:

InputValue
Target rate constant with HO•, L/(mol·s)1.4000e+10 -
Target rate constant with ozone, L/(mol·s)10.000 -
Ratio [HO•]/[O₃]1.0000e-08 -
Initial dissolved ozone3.0000 mg/L
Ozone decay rate constant0.10000 1/min
Target removal95.000 %

Applying the formula below gives:

ResultValue
Share of destruction by hydroxyl radicals93.333 %
Effective rate constant, L/(mol·s)150.00
Initial ozone, mol/L6.2503e-05
Largest removal possible before the ozone is gone (as ln)5.6252
Half-life of the target1.3150 min
Time for the target removal7.6047 min

Open this example in the calculator and change any input.

Formula

\(f_{HO\bullet} = \frac{k_{HO\bullet}R_{ct}}{k_{HO\bullet}R_{ct} + k_{O_3}}, \quad \ln\frac{[R]_0}{[R]} = \frac{[O_3]_0}{k}\left(k_{HO\bullet}R_{ct} + k_{O_3}\right)\left(1 - e^{-kt}\right)\)

\(t_X = -\frac{1}{k}\ln\left[1 + \frac{k\ln(1 - X)}{[O_3]_0(k_{HO\bullet}R_{ct} + k_{O_3})}\right]\)

Variables

Symbol Meaning SI unit
\(k_{HO\bullet}\) Target rate constant with HO•, L/(mol·s) -
\(k_{O_3}\) Target rate constant with ozone, L/(mol·s) -
\(R_{ct}\) Ratio [HO•]/[O₃] -
\([O_3]_0\) Initial dissolved ozone kg/m³
\(k\) Ozone decay rate constant 1/s
\(X\) Target removal -
\(f_{HO\bullet}\) Share of destruction by hydroxyl radicals -
\(k_{HO\bullet}R_{ct} + k_{O_3}\) Effective rate constant, L/(mol·s) -
\(\ln(R_0/R)_{max}\) Largest removal possible before the ozone is gone (as ln) -
\(t_{1/2}\) Half-life of the target s
\(t_X\) Time for the target removal s

Method and standards

Combined direct ozone and hydroxyl radical oxidation with first-order ozone decay.

Where it is used

  • Taste-and-odour and micropollutant control by ozone.
  • Choosing ozone dose and contact time.

Common mistakes

  • Ignoring ozone decay.
  • Assuming direct ozone reaction dominates for saturated compounds.

Assumptions and limits

  • Constant R_ct; batch or plug flow.

Questions and answers

Why do taste and odour compounds go mainly by hydroxyl radicals?

Geosmin and MIB react with ozone only about 10 L/(mol·s) but with HO• around 10¹⁰, so even R_ct = 10⁻⁸ makes the radical path dominant.

What limits the removal?

Ozone decays: the largest achievable ln(R₀/R) is [O₃]₀(k_HO•R_ct + k_O₃)/k.

What do the defaults represent?

An illustrative case: Geosmin with Rct 1e-8. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 18-2, eqs. 18-20 to 18-26 and Examples 18-4 and 18-5 (Elovitz and von Gunten 1999)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.