Membrane Filtration Plant Sizing from Pilot Data

Online production factor, recovery, feed flow, membrane area, modules and racks of a low-pressure membrane plant from pilot flux, backwash, testing and cleaning.

Inputs

Examples: Cold-water design 20,000 m3/d at 45 LMH, 30 + 1.5 min, 80 L, 38 m2, CIP 6 h every 21 dSmall 2,000 m3/d at 70 LMH, 60 + 1 min, 120 L, 64 m2, 40 per rack

Accepted: 8.64 to 8,640,000 m³/d
Accepted: 3.6 to 3,600 L/(m²·h)
Accepted: 1 to 600 min
Accepted: 0.016667 to 60 min
Accepted: 0 to 10,000 L
Accepted: 1 to 500 m²
Accepted: 0 to 120 min
Accepted: 0 to 48 h
Accepted: 1 to 365
Accepted: 1 to 1,000

Results

Design flux at the lowest water temperature should govern. Add spare racks so the plant still meets demand with one rack in cleaning or repair.

Online production factor97.250%
System recovery97.321%
Feed flow2,055.0m³/d
Membrane area required1,257.8m²
Modules required20.000
Racks1.0000
Modules per rack (equal racks)20.000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Cold-water design 20,000 m3/d at 45 LMH, 30 + 1.5 min, 80 L, 38 m2, CIP 6 h every 21 d. The inputs, in the units selected above:

InputValue
Net permeate production20,000 m³/d
Design flux at the design temperature45.000 L/(m²·h)
Filtration time per cycle30.000 min
Backwash time per cycle1.5000 min
Backwash volume per module80.000 L
Membrane area per module38.000 m²
Integrity test time per day15.000 min
Duration of one clean-in-place6.0000 h
Days between cleanings21.000 -
Maximum modules per rack80.000 -

Applying the formula below gives:

ResultValue
Online production factor93.006 %
System recovery90.643 %
Feed flow22,065 m³/d
Membrane area required21,966 m²
Modules required579.00
Racks8.0000
Modules per rack (equal racks)73.000

Open this example in the calculator and change any input.

Formula

\(\eta = \frac{1440 - t_{bw} - t_{dit} - t_{cip}}{1440}, \quad r = \frac{Jat_f - V_{bw}}{Jat_f}\)

\(Q_f = \frac{Q_p}{r}, \quad A = \frac{Q_f}{J\eta}\)

Variables

Symbol Meaning SI unit
\(Q_p\) Net permeate production m³/s
\(J\) Design flux at the design temperature m/s
\(t_f\) Filtration time per cycle s
\(t_{bw}\) Backwash time per cycle s
\(V_{bw}\) Backwash volume per module m³
\(a_m\) Membrane area per module m²
\(t_{dit}\) Integrity test time per day s
\(t_{cip}\) Duration of one clean-in-place s
\(t_{int}\) Days between cleanings -
\(n_{rack}\) Maximum modules per rack -
\(\eta\) Online production factor -
\(r\) System recovery -
\(Q_f\) Feed flow m³/s
\(A\) Membrane area required m²
\(N_{mod}\) Modules required -
\(N_{rack}\) Racks -
\(n\) Modules per rack (equal racks) -

Method and standards

Time-averaged production and recovery of a backwashed membrane system.

Where it is used

  • Preliminary sizing of UF and MF plants.
  • Checking vendor proposals.

Common mistakes

  • Designing at the warm-water flux.
  • Forgetting the integrity test and cleaning downtime.

Assumptions and limits

  • Constant flux operation; backwash with permeate.

Questions and answers

Why does recovery use the module backwash volume?

Every module loses its own backwash water each cycle, so recovery is the same for one module as for the plant.

What sets the design flux?

Pilot testing at the coldest expected water; typical low-pressure membrane fluxes are 40–100 L/(m²·h).

What do the defaults represent?

An illustrative case: Cold-water design 20,000 m3/d at 45 LMH, 30 + 1.5 min, 80 L, 38 m2, CIP 6 h every 21 d. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 12-7, eq. 12-26 and Example 12-8

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.