FireCADCalc

Kolmogorov Microscale from Mixing Intensity G

Energy dissipation rate and Kolmogorov smallest eddy size in a mixed tank from the velocity gradient G or the power input and volume.

Inputs

Examples: G 100 1/s at 10 CRapid mix G 1,000 1/s at 20 C

Accepted: 0.1 to 10,000 1/s
Accepted: 1E-5 to 10,000 kW
Accepted: 0.001 to 100,000 m³
Accepted: 2E-7 to 2E-6 m²/s
Accepted: 900 to 1,100 kg/m³

Results

ε is in W/kg (shown as J/kg per second). Particles smaller than the Kolmogorov scale are moved by viscous shear (microscale flocculation); larger ones by turbulent eddies. Uniform dissipation (ε = mean) is assumed; near the impeller ε is far higher.

Velocity gradient1,000.01/s
Energy dissipation rate per unit mass1.0030J/kg
Kolmogorov microscale31.670µm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: G 100 1/s at 10 C. The inputs, in the units selected above:

InputValue
Mixing given asVelocity gradient G
Velocity gradient100.00 1/s
Power input to the water0.54600 kW
Tank volume65.100 m³
Kinematic viscosity1.3100e-06 m²/s
Density999.70 kg/m³

Applying the formula below gives:

ResultValue
Velocity gradient100.00 1/s
Energy dissipation rate per unit mass0.013100 J/kg
Kolmogorov microscale114.46 µm

Open this example in the calculator and change any input.

Formula

\(\varepsilon = \frac{P}{\rho V} = G^2\nu, \quad \eta_K = \left(\frac{\nu^3}{\varepsilon}\right)^{1/4} = \left(\frac{\nu}{G}\right)^{1/2}\)

Variables

Symbol Meaning SI unit
\(\text{input}\) Mixing given as -
\(G\) Velocity gradient 1/s
\(P\) Power input to the water W
\(V\) Tank volume m³
\(\nu\) Kinematic viscosity m²/s
\(\rho\) Density kg/m³
\(\varepsilon\) Energy dissipation rate per unit mass J/kg
\(\eta_K\) Kolmogorov microscale m

Method and standards

Kolmogorov scaling of turbulence.

Where it is used

  • Rapid mix and flocculator design.
  • Relating floc size limits to mixing.

Common mistakes

  • Using dynamic viscosity in place of kinematic.
  • Assuming the average ε holds near the impeller.

Assumptions and limits

  • Isotropic turbulence, uniform dissipation.

Questions and answers

Why does it matter for flocculation?

Flocs smaller than the microscale see laminar shear; those larger are torn by eddies, which limits floc size at high G.

How does it change with G?

η = (ν/G)^½, so a hundredfold rise in G shrinks the smallest eddies tenfold.

What do the defaults represent?

An illustrative case: G 100 1/s at 10 C. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 6-10, eqs. 6-136 to 6-140 and Example 6-10

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.