Worked example
Example: Illustrative: 1.5 mg/L ClO2, 65 % to chlorite, 0.2 mg/L target, 20 % excess. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Chlorine dioxide dose | 1.5000 mg/L |
| Share of the dose that becomes chlorite | 65.000 % |
| Chlorite allowed after treatment | 0.20000 mg/L |
| Excess ferrous iron over stoichiometric | 20.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Chlorite formed | 0.97500 mg/L |
| Chlorite to remove | 0.77500 mg/L |
| Stoichiometric iron per chlorite, mg/mg | 3.3117 |
| Ferrous iron dose | 3.0799 mg/L |
| As ferrous sulphate heptahydrate | 15.332 mg/L |
Open this example in the calculator and change any input.
Formula
\(C_{ClO_2^-} = f\,C_{ClO_2}, \quad C_{Fe} = (C_{ClO_2^-} - C_{target})\frac{4M_{Fe}}{M_{ClO_2^-}}(1 + \chi)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_{ClO_2}\) | Chlorine dioxide dose | kg/m³ |
| \(f\) | Share of the dose that becomes chlorite | - |
| \(C_{target}\) | Chlorite allowed after treatment | kg/m³ |
| \(\chi\) | Excess ferrous iron over stoichiometric | - |
| \(C_{ClO_2^-}\) | Chlorite formed | kg/m³ |
| \(\Delta C\) | Chlorite to remove | kg/m³ |
| \(Fe/ClO_2^-\) | Stoichiometric iron per chlorite, mg/mg | - |
| \(C_{Fe}\) | Ferrous iron dose | kg/m³ |
| \(C_{FeSO_4\cdot7H_2O}\) | As ferrous sulphate heptahydrate | kg/m³ |
Method and standards
Reduction of chlorite by ferrous iron.
Where it is used
- Plants using chlorine dioxide pre-oxidation.
- Meeting the chlorite limit (1.0 mg/L in the US).
Common mistakes
- Using the chlorine dioxide dose as the chlorite to remove.
- Forgetting the iron load on the filters.
Assumptions and limits
- Stoichiometric reaction; pH 5–7 for fast reaction.
References
- Stoichiometry 4Fe²⁺ + ClO₂⁻ → 4Fe³⁺ + Cl⁻
Questions and answers
How much chlorite does chlorine dioxide form?
Typically 50–70 % of the dose, depending on the oxidant demand of the water; the rest becomes chloride and some chlorate.
Why add excess iron?
Dissolved oxygen and other oxidants also consume ferrous iron, so a 10–30 % excess is usual; excess iron must not pass the filters.
What do the defaults represent?
An illustrative pre-oxidation: 1.5 mg/L of chlorine dioxide with 65 % converting to chlorite, to be reduced to 0.2 mg/L with 20 % excess iron.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 19-4, eq. 19-14 and Example 19-4