Worked example
Example: Groundwater: TCE 100 ug/L, 1 mg/L DOC, 4 mmol/L carbonate at pH 8, 0.5 mg/L Fe, 0.1 mg/L Mn. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Target rate constant with HO•, L/(mol·s) | 4.2000e+09 - |
| Target concentration | 100.00 µg/L |
| Target molar mass | 131.39 kg/kmol |
| NOM as dissolved organic carbon | 1.0000 mg/L |
| NOM rate constant, L/(mol C·s) | 3.9000e+08 - |
| Total carbonate | 4.0000 mmol/L |
| pH | 8.0000 - |
| Iron(II) | 0.50000 mg/L |
| Manganese(II) | 0.10000 mg/L |
| Hydroxyl radical concentration, mol/L | 1.0000e-10 - |
| Target removal | 99.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Target concentration, mol/L | 7.6109e-07 |
| Rate of HO• use by the target, 1/s | 3,196.6 |
| HO• scavenging by NOM, 1/s | 32,470 |
| HO• scavenging by carbonate species, 1/s | 40,800 |
| HO• scavenging by Fe(II) and Mn(II), 1/s | 3,009.2 |
| Share of HO• reacting with the target | 4.0221 % |
| Pseudo-first-order rate k_R C_HO• | 0.42000 1/s |
| Half-life of the target | 1.6504 s |
| Time for the target removal (batch or PFR) | 0.18274 min |
Open this example in the calculator and change any input.
Formula
\(Q_R = \frac{k_RC_R}{k_RC_R + k_{NOM}C_{DOC} + k_{HCO_3^-}C_{HCO_3^-} + k_{CO_3^{2-}}C_{CO_3^{2-}} + k_{Fe}C_{Fe} + k_{Mn}C_{Mn}}\)
\(t_{1/2} = \frac{\ln 2}{k_RC_{HO\bullet}}, \quad t_X = \frac{-\ln(1 - X)}{k_RC_{HO\bullet}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(k_R\) | Target rate constant with HO•, L/(mol·s) | - |
| \(C_R\) | Target concentration | kg/m³ |
| \(M_R\) | Target molar mass | kg/kmol |
| \(C_{DOC}\) | NOM as dissolved organic carbon | kg/m³ |
| \(k_{NOM}\) | NOM rate constant, L/(mol C·s) | - |
| \(C_{T,CO_3}\) | Total carbonate | mol/m³ |
| \(pH\) | pH | - |
| \(C_{Fe(II)}\) | Iron(II) | kg/m³ |
| \(C_{Mn(II)}\) | Manganese(II) | kg/m³ |
| \(C_{HO\bullet}\) | Hydroxyl radical concentration, mol/L | - |
| \(X\) | Target removal | - |
| \(k_RC_R\) | Rate of HO• use by the target, 1/s | - |
| \(k_{NOM}C_{DOC}\) | HO• scavenging by NOM, 1/s | - |
| \(k_{HCO_3}[HCO_3^-] + k_{CO_3}[CO_3^{2-}]\) | HO• scavenging by carbonate species, 1/s | - |
| \(k_{Fe}C_{Fe} + k_{Mn}C_{Mn}\) | HO• scavenging by Fe(II) and Mn(II), 1/s | - |
| \(Q_R\) | Share of HO• reacting with the target | - |
| \(k\) | Pseudo-first-order rate k_R C_HO• | 1/s |
| \(t_{1/2}\) | Half-life of the target | s |
| \(t_X\) | Time for the target removal (batch or PFR) | s |
Method and standards
Competition kinetics for hydroxyl radicals between the target and background scavengers.
Where it is used
- Feasibility of UV/H₂O₂, O₃/H₂O₂ and other AOPs.
- Planning AOP bench tests in the real water.
Common mistakes
- Testing in distilled water and scaling to the field.
- Ignoring carbonate at high pH.
Assumptions and limits
- Second-order kinetics; scavengers in excess and unchanged.
Questions and answers
Why does tap water behave so differently from lab water?
NOM consumes hydroxyl radicals: mg/L of DOC cuts the share reaching TCE from 47 % to 1.5 %.
What hydroxyl radical concentration is realistic?
About 10⁻¹¹ to 10⁻⁹ mol/L; at 10⁻¹¹ even fast-reacting compounds need minutes.
What do the defaults represent?
An illustrative case: Groundwater: TCE 100 ug/L, 1 mg/L DOC, 4 mmol/L carbonate at pH 8, 0.5 mg/L Fe, 0.1 mg/L Mn. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 18-1, eqs. 18-2 to 18-8, Table 18-2 and Examples 18-1 to 18-3