Worked example
Example: Blowdown 2 t/h from 45 bar(a) to 2 bar(a), K 0.05. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Blowdown or condensate entering | 2,000.0 kg/h |
| Pressure before flashing (absolute) | 45.000 bar |
| Flash vessel pressure (absolute) | 2.0000 bar |
| Souders–Brown velocity factor | 0.050000 m/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Minimum inside diameter of the vessel | 348.83 mm |
| Allowable vapour velocity | 1.4441 m/s |
| Flash steam | 560.93 kg/h |
| Flash fraction | 28.046 % |
| Flash steam volume flow | 496.83 m³/h |
| Steam density in the vessel | 1.1290 kg/m³ |
| Water density in the vessel | 942.94 kg/m³ |
Open this example in the calculator and change any input.
Formula
\(x = \frac{h_{f,1} - h_{f,f}}{h_{fg,f}} \qquad \dot m_{fs} = x\,\dot m \qquad \dot V_v = \frac{\dot m_{fs}}{\rho_v}\)
\(u_{max} = K\sqrt{\frac{\rho_l - \rho_v}{\rho_v}} \qquad D = \sqrt{\frac{4\,\dot V_v}{\pi\,u_{max}}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | blowdown or condensate entering | kg/s |
| \(p_1\) | pressure before flashing, absolute | Pa |
| \(p_f\) | flash vessel pressure, absolute | Pa |
| \(K\) | Souders–Brown velocity factor | m/s |
| \(D\) | minimum inside diameter | m |
| \(u_{max}\) | allowable vapour velocity | m/s |
| \(\dot m_{fs}\) | flash steam | kg/s |
| \(x\) | flash fraction | – |
| \(\dot V_v\) | flash steam volume flow | m³/s |
| \(\rho_v\) | steam density in the vessel | kg/m³ |
| \(\rho_l\) | water density in the vessel | kg/m³ |
| \(h_{f,1}\) | saturated water enthalpy before flashing | J/kg |
| \(h_{f,f}\) | saturated water enthalpy at vessel pressure | J/kg |
| \(h_{fg,f}\) | latent heat at vessel pressure | J/kg |
Method and standards
Flash fraction from the energy balance with FireCAD's IAPWS-IF97 saturation properties; allowable vapour velocity by the Souders–Brown equation (Souders and Brown, 1934), as used for vertical vapour–liquid separators in the GPSA Engineering Data Book.
Where it is used
- Blowdown flash vessels and condensate flash recovery.
- Low-pressure steam recovery to deaerators and heaters.
- Checking an existing vessel for a higher blowdown rate.
Common mistakes
- Using gauge pressures in the flash calculation.
- Choosing too high a vapour velocity, which carries water over.
- Forgetting the vent and drain sizes.
Assumptions and limits
- Water saturated at the upstream pressure; subcooled condensate flashes less.
- Vertical vessel, vapour flowing upward over the full cross-section.
- The K factor is your design choice; the calculator does not check carry-over (a note appears above 0.15 m/s).
- The diameter is the bare minimum: no design margin, inlet momentum or droplet-loading allowance is added.
References
- Souders and Brown (1934)
- GPSA Engineering Data Book (separator K values)
- IAPWS R7-97(2012) IF97
Questions and answers
How do I size a flash vessel?
Find the flash steam, then the allowable vapour velocity u = K·√((ρ_l − ρ_v)/ρ_v), and the diameter that passes the steam at that velocity. 2 t/h of blowdown from 45 bar(a) to 2 bar(a) flashes 28 % (561 kg/h); with K = 0.05 m/s the velocity is 1.44 m/s and the vessel needs 349 mm.
Which K value?
It sets how much water the steam carries over. The GPSA data book gives about 0.1 m/s for vertical separators with a wire-mesh demister; vessels without one use about half. Enter your design value.
What about the height?
The calculator gives the diameter. Height comes from the inlet arrangement, the disengagement space above it and the water hold-up below, from your vessel standard.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.