FireCADCalc

Wobbe Index and Gas Interchangeability

Wobbe index of two fuel gases from their gross calorific value and relative density, and the change in burner heat input when one replaces the other.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalPulp and paperFuel oil and gas systemBurner and furnace

Inputs

Examples: Pipeline NG vs RLNGNG vs propane-air mixTwo NG supplies

Results

Wobbe index, gas now50.349MJ/Nm³
Wobbe index, new gas52.285MJ/Nm³
Heat input ratio at the same burner pressure1.0385
Change in Wobbe index3.8458%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Pipeline NG vs RLNG. The inputs, in the units selected above:

InputValue
Gross calorific value, gas now39.000 MJ/Nm³
Relative density (air = 1), gas now0.60000 -
Gross calorific value, new gas41.500 MJ/Nm³
Relative density (air = 1), new gas0.63000 -

Applying the formula below gives:

ResultValue
Wobbe index, gas now50.349 MJ/Nm³
Wobbe index, new gas52.285 MJ/Nm³
Heat input ratio at the same burner pressure1.0385
Change in Wobbe index3.8458 %

Open this example in the calculator and change any input.

Formula

\(W = \frac{H}{\sqrt{d}} \qquad \frac{W_2}{W_1} = \frac{\dot Q_2}{\dot Q_1}\ \text{(same orifice and pressure)} \qquad \Delta W = \frac{W_2}{W_1} - 1\)

Variables

Symbol Meaning SI unit
\(H_1\), \(H_2\) gross calorific value, gas now and new gas J/m³
\(d_1\), \(d_2\) relative density (air = 1) –
\(W_1\) Wobbe index, gas now J/m³
\(W_2\) Wobbe index, new gas J/m³
\(W_2/W_1\) heat input ratio –
\(\Delta W\) change in Wobbe index –
\(W\), \(H\), \(d\) Wobbe index, calorific value, relative density in general J/m³, J/m³, –
\(\dot Q\) burner heat input W

Method and standards

Definition of the Wobbe index; flow through an orifice at fixed pressure scales with 1/√d, so heat input scales with W.

Where it is used

  • Switching between pipeline gas, RLNG and LPG-air.
  • Checking a new gas supply before changing burners.
  • Gas quality specifications.

Common mistakes

  • Comparing gases on calorific value alone.
  • Mixing gross and net calorific values in the two indices.
  • Using density instead of relative density.

Assumptions and limits

  • Same burner, orifice and supply pressure and temperature; combustion stability, lift and yellow-tipping indices not covered.
  • The 5 % warning is a FireCAD prompt, not a sourced limit: interchangeability limits come from your national gas quality rules and the burner maker.

References

  • Wobbe index definition W = HHV / √d

Questions and answers

What is the Wobbe index?

Gross calorific value divided by the square root of relative density. Gases with the same Wobbe index give the same heat input through the same burner orifice at the same pressure.

What happens if the gas changes?

Heat input changes by the Wobbe ratio. Pipeline gas at 39.0 MJ/Nm³ and d = 0.60 (W = 50.4) replaced by gas at 41.5 MJ/Nm³ and d = 0.63 (W = 52.3) raises heat input 3.8 % at the same pressure.

How much change is acceptable?

It depends on the burner; many gas utilities work within a few per cent. Larger changes need re-setting the air–gas ratio or new orifices; ask the burner maker.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.