Worked example
Example: Pipeline NG vs RLNG. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gross calorific value, gas now | 39.000 MJ/Nm³ |
| Relative density (air = 1), gas now | 0.60000 - |
| Gross calorific value, new gas | 41.500 MJ/Nm³ |
| Relative density (air = 1), new gas | 0.63000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Wobbe index, gas now | 50.349 MJ/Nm³ |
| Wobbe index, new gas | 52.285 MJ/Nm³ |
| Heat input ratio at the same burner pressure | 1.0385 |
| Change in Wobbe index | 3.8458 % |
Open this example in the calculator and change any input.
Formula
\(W = \frac{H}{\sqrt{d}} \qquad \frac{W_2}{W_1} = \frac{\dot Q_2}{\dot Q_1}\ \text{(same orifice and pressure)} \qquad \Delta W = \frac{W_2}{W_1} - 1\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(H_1\), \(H_2\) | gross calorific value, gas now and new gas | J/m³ |
| \(d_1\), \(d_2\) | relative density (air = 1) | – |
| \(W_1\) | Wobbe index, gas now | J/m³ |
| \(W_2\) | Wobbe index, new gas | J/m³ |
| \(W_2/W_1\) | heat input ratio | – |
| \(\Delta W\) | change in Wobbe index | – |
| \(W\), \(H\), \(d\) | Wobbe index, calorific value, relative density in general | J/m³, J/m³, – |
| \(\dot Q\) | burner heat input | W |
Method and standards
Definition of the Wobbe index; flow through an orifice at fixed pressure scales with 1/√d, so heat input scales with W.
Where it is used
- Switching between pipeline gas, RLNG and LPG-air.
- Checking a new gas supply before changing burners.
- Gas quality specifications.
Common mistakes
- Comparing gases on calorific value alone.
- Mixing gross and net calorific values in the two indices.
- Using density instead of relative density.
Assumptions and limits
- Same burner, orifice and supply pressure and temperature; combustion stability, lift and yellow-tipping indices not covered.
- The 5 % warning is a FireCAD prompt, not a sourced limit: interchangeability limits come from your national gas quality rules and the burner maker.
References
- Wobbe index definition W = HHV / √d
Questions and answers
What is the Wobbe index?
Gross calorific value divided by the square root of relative density. Gases with the same Wobbe index give the same heat input through the same burner orifice at the same pressure.
What happens if the gas changes?
Heat input changes by the Wobbe ratio. Pipeline gas at 39.0 MJ/Nm³ and d = 0.60 (W = 50.4) replaced by gas at 41.5 MJ/Nm³ and d = 0.63 (W = 52.3) raises heat input 3.8 % at the same pressure.
How much change is acceptable?
It depends on the burner; many gas utilities work within a few per cent. Larger changes need re-setting the air–gas ratio or new orifices; ask the burner maker.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.