Worked example
Example: NG 1000 Nm³/h, 4 bar(a), 100 mm, 500 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gas flow at normal conditions | 1,000.0 Nm³/h |
| Molar mass of the gas | 17.400 kg/kmol |
| Gas dynamic viscosity | 1.1000e-05 Pa·s |
| Inlet pressure (absolute) | 4.0000 bar |
| Gas temperature | 20.000 °C |
| Pipe inside diameter | 102.30 mm |
| Pipe length (with fittings as equivalent length) | 500.00 m |
| Pipe roughness | 0.046000 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Outlet pressure (absolute) | 3.8911 bar |
| Pressure drop | 10.889 kPa |
| Inlet velocity | 9.1876 m/s |
| Outlet velocity | 9.4447 m/s |
| Reynolds number | 243,989 |
| Darcy friction factor | 0.018223 |
Open this example in the calculator and change any input.
Formula
\(G = \frac{\dot V_n\,\rho_n}{\pi D^2/4} \qquad Re = \frac{G\,D}{\mu} \qquad f = f_{Colebrook}(Re, \varepsilon/D)\)
\(p_1^2 - p_2^2 = \frac{G^2\,R\,T}{M}\left(\frac{f\,L}{D} + 2\ln\frac{p_1}{p_2}\right) \qquad v_1 = \frac{G}{\rho_1} \qquad v_2 = \frac{G}{\rho_2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_n\) | gas flow at normal conditions | Nm³/s |
| \(M\) | molar mass of the gas | kg/kmol |
| \(\mu\) | dynamic viscosity | Pa·s |
| \(p_1\) | inlet pressure, absolute | Pa |
| \(T\) | gas temperature | K |
| \(D\) | pipe inside diameter | m |
| \(L\) | pipe length with equivalent length of fittings | m |
| \(\varepsilon\) | pipe roughness | m |
| \(p_2\) | outlet pressure, absolute | Pa |
| \(\Delta p\) | pressure drop | Pa |
| \(v_1\) | inlet velocity | m/s |
| \(v_2\) | outlet velocity | m/s |
| \(\rho_2\) | density at outlet conditions | kg/m³ |
| \(Re\) | Reynolds number | – |
| \(f\) | Darcy friction factor | – |
| \(G\) | mass flux | kg/(m²·s) |
| \(\rho_n\), \(\rho_1\) | density at normal and at inlet conditions | kg/m³ |
| \(R\) | universal gas constant | J/(kmol·K) |
Method and standards
Steady isothermal flow of an ideal gas in a constant-area pipe with the Darcy friction factor from the Colebrook–White equation (FireCAD Friction); the outlet pressure is found by bracketed root solving.
Where it is used
- Sizing gas supply lines from the meter station to boilers and furnaces.
- Checking pressure at the burner gas train inlet.
- Long gas headers in process plants.
Common mistakes
- Using gauge pressures in a squared-pressure equation.
- Leaving out fittings and valves.
- Using normal density in the velocity check.
Assumptions and limits
- Isothermal ideal gas (Z = 1); horizontal pipe; flow below choking. Above about 10 bar natural gas departs from Z = 1 and a warning appears.
- The friction factor uses Colebrook in the 2300–4000 transition range (conservative).
- Normal volumes are at 0 °C and 101.325 kPa; scfm is converted to the US standard cubic foot (60 °F, 14.696 psia).
- Isothermal flow chokes when the outlet pressure falls to \(G\sqrt{RT/M}\) (velocity \(\sqrt{RT/M}\)); if the equation has no solution above that pressure, the line is reported as choked.
References
- Isothermal compressible flow in pipes (Darcy–Weisbach form)
- Colebrook–White friction factor
Questions and answers
How do I calculate gas pipeline pressure drop?
With the isothermal flow equation, which allows for the gas expanding as pressure falls. 1000 Nm³/h of natural gas at 4 bar(a) through 500 m of 100 mm pipe loses 10.9 kPa; the gas enters at 9.2 m/s.
Can I use the liquid (Darcy) formula?
Only for small pressure drops (under about 10 % of the inlet pressure) using an average density; the isothermal equation is right for any drop short of choking.
What molar mass for natural gas?
From the gas analysis; typical pipeline gas is 16–18.5 kg/kmol (relative density 0.56–0.64).
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.