FireCADCalc

Combustion Air and Flue Gas Flow

Combustion air and flue gas flows for a firing rate: kg/h, Nm³/h and actual m³/h at the fan and duct temperatures, from the fuel analysis and excess air.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalThermic fluid heatingPulp and paperASME PTC 4 (fired steam generators)BoilerBurner and furnaceStack and chimney

Inputs

Examples: Indian coal 12 t/h, 25 % excess air, gas 140 °CFuel oil 2 t/h, 15 % excess air, gas 170 °CBagasse 25 t/h, 30 % excess air, gas 160 °C, site 0.95 bar

Ultimate analysis, as fired, by mass

Absolute. For a site above sea level use the site barometric pressure.

Results

Dry combustion air92,787kg/h
Wet combustion air (with its moisture)93,993kg/h
Wet air, normal volume (0 °C, 1 atm)73,300Nm³/h
Wet air, actual volume at the air temperature81,350m³/h
Wet flue gas101,793kg/h
Wet flue gas, normal volume77,644Nm³/h
Dry flue gas, normal volume69,980Nm³/h
Wet flue gas, actual volume at the gas temperature117,439m³/h
Dry air per kg of fuel7.7323kg/kg
O₂ in dry flue gas (analyser reading)4.2989%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Indian coal 12 t/h, 25 % excess air, gas 140 °C. The inputs, in the units selected above:

InputValue
Carbon45.000 %
Hydrogen3.5000 %
Oxygen5.0000 %
Nitrogen1.0000 %
Sulphur0.50000 %
Ash35.000 %
Moisture10.000 %
Fuel firing rate12,000 kg/h
Excess air25.000 %
Air humidity (kg water per kg dry air)0.013000 kg/kg
Air temperature (at the FD fan)30.000 °C
Flue gas temperature (at the ID fan or duct)140.00 °C
Pressure in the duct (absolute)1.0132 bar

Applying the formula below gives:

ResultValue
Dry combustion air92,787 kg/h
Wet combustion air (with its moisture)93,993 kg/h
Wet air, normal volume (0 °C, 1 atm)73,300 Nm³/h
Wet air, actual volume at the air temperature81,350 m³/h
Wet flue gas101,793 kg/h
Wet flue gas, normal volume77,644 Nm³/h
Dry flue gas, normal volume69,980 Nm³/h
Wet flue gas, actual volume at the gas temperature117,439 m³/h
Dry air per kg of fuel7.7323 kg/kg
O₂ in dry flue gas (analyser reading)4.2989 %

Open this example in the calculator and change any input.

Formula

Per kg of fuel, with exact molar ratios and ASME PTC 4 air (20.95 % O₂ by volume):

\(m_a = \frac{\tfrac{M_{O_2}}{M_C}C + \tfrac{M_{O_2}}{2M_{H_2}}H + \tfrac{M_{O_2}}{M_S}S - O}{w_{O_2}}\,(1 + EA), \quad M_{O_2} = 31.998,\ M_C = 12.011,\ M_{H_2} = 2.016,\ M_S = 32.06\)

\(\dot m_a = \dot m_f\, m_a \qquad \dot m_g = \dot m_f\,(m_{CO_2} + m_{H_2O} + m_{SO_2} + m_{N_2} + m_{O_2})\)

\(\dot V_N = \dot n\,V_{m,N} \qquad \dot V = \dot n\,\frac{R\,T}{p}\)

Variables

Symbol Meaning SI unit
\(C\), \(H\), \(O\), \(N\), \(S\) carbon, hydrogen, oxygen, nitrogen, sulphur in the fuel as fired –
\(A\) ash –
\(M\) moisture –
\(\dot m_f\) fuel firing rate kg/s
\(EA\) excess air –
\(\omega\) air humidity, kg water per kg dry air kg/kg
\(T_a\) air temperature at the FD fan K
\(T_g\) flue gas temperature at the ID fan or duct K
\(p\) absolute pressure in the duct Pa
\(\dot m_a\) dry combustion air kg/s
\(\dot m_{a,wet}\) wet combustion air kg/s
\(\dot V_{a,N}\) wet air at 0 °C, 101.325 kPa Nm³/s
\(\dot V_a\) wet air at the air temperature m³/s
\(\dot m_g\) wet flue gas kg/s
\(\dot V_{g,N}\) wet flue gas, normal volume Nm³/s
\(\dot V_{g,dry,N}\) dry flue gas, normal volume Nm³/s
\(\dot V_g\) wet flue gas at the gas temperature m³/s
\(m_a\) dry air per kg of fuel kg/kg
\(y_{O_2,dry}\) O₂ in dry flue gas, \(\dfrac{m_{O_2}/M_{O_2}}{\dot n_{g,dry}/\dot m_f}\) (excess oxygen moles over dry gas moles) –
\(m_{CO_2}\), \(m_{H_2O}\), \(m_{SO_2}\), \(m_{N_2}\), \(m_{O_2}\) flue gas species per kg of fuel: CO₂, water vapour (from hydrogen, fuel moisture and air humidity), SO₂, nitrogen with argon and air CO₂, excess O₂ kg/kg
\(M_i\) molar masses (IUPAC) kg/kmol
\(w_{O_2}\) mass fraction of O₂ in dry air (23.15 %) –
\(\dot n\) molar flow of air or gas kmol/s
\(V_{m,N}\) molar volume at 0 °C, 101.325 kPa (22.414 m³/kmol) m³/kmol
\(R\) universal gas constant J/(mol·K)

Method and standards

The mass balance is the same as the combustion calculator: exact molar ratios from IUPAC atomic weights and the ASME PTC 4-2013 air composition, with argon and CO₂ of air carried as "atmospheric nitrogen". Volumes follow from the molar flows: normal volumes with the ideal-gas molar volume at 0 °C and 101.325 kPa (CODATA 2018), actual volumes with the ideal-gas law at the temperature and pressure entered.

Where it is used

  • Sizing FD and SA fans and air ducts.
  • Setting air flow for a firing rate.
  • Checking combustion air at site altitude.

Common mistakes

  • Forgetting excess air and air heater leakage.
  • Mixing normal and actual volumes.
  • Using dry air when the air carries moisture.

Assumptions and limits

  • Complete combustion; no CO or unburned carbon.
  • Ideal gas; adequate for air and flue gas at duct pressures.
  • Air in-leakage between the boiler and the ID fan is not included; raise the excess air to the value at the point considered.
  • Fly ash is not part of the gas flow.
  • One pressure is used for both the air and the gas volumes; the FD fan discharge is above and the ID fan inlet below atmospheric, so run the calculator once with each pressure for the two fans.
  • All the water is treated as vapour; below the water dew point of the gas (a warning appears) the actual gas volume is overstated.
  • Normal volumes are at 0 °C and 101.325 kPa; scfm is converted to the US standard cubic foot (60 °F, 14.696 psia).

References

  • ASME PTC 4-2013 (air composition)
  • IUPAC atomic weights

Questions and answers

How much air does a coal boiler need?

For an Indian coal with 45 % carbon and 35 % ash, 6.19 kg of dry air per kg of coal is stoichiometric and 7.73 kg/kg with 25 % excess air. A 12 t/h firing rate needs 25.8 kg/s of dry air, 73 300 Nm³/h of wet air.

What is the difference between Nm³/h and actual m³/h?

Nm³/h is the volume at 0 °C and 101.325 kPa and does not change along the duct. Fans move actual m³/h, the volume at the local temperature and pressure; at 140 °C flue gas occupies about 1.5 times its normal volume.

Does the flue gas mass include ash?

No. The flue gas is the gaseous products plus excess air and moisture; fly ash leaves with the gas but is not part of its mass or volume here.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.