Boiler Surface Radiation and Convection Loss

Heat lost from a boiler casing by natural convection and radiation from its area and surface temperature (ISO 12241 vertical-wall equations), as a share of heat input.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationThermic fluid heatingPulp and paperFood, dairy and textileASME PTC 4 (fired steam generators)ISO 12241 (thermal insulation)Boiler

Inputs

Examples: Boiler casing 400 m², 55 °C, aluminium cladding, 12 m high, 80 MW inputPackage boiler 60 m², 60 °C, painted, 3 m high, 6 MWHot spot test: 2 m², 150 °C, 1 m

Measure with an infrared thermometer at many points and average by area.
Aluminium cladding about 0.05–0.15, galvanised steel 0.25, painted surfaces about 0.9.

Results

Surface loss, % of heat input0.44701%
Heat lost from the surface4.4701kW
Heat loss per m²2,235.1W/m²
Convection coefficient8.5824W/(m²·K)
Radiation coefficient10.043W/(m²·K)

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Boiler casing 400 m², 55 °C, aluminium cladding, 12 m high, 80 MW input. The inputs, in the units selected above:

InputValue
Outer surface area of casing, ducts and headers400.00 m²
Mean outer surface temperature55.000 °C
Surrounding air temperature30.000 °C
Emissivity of the surface0.15000 -
Height of the walls12.000 m
Heat input from fuel (for the % loss; on the basis of your efficiency, GCV or NCV)80.000 MW

Applying the formula below gives:

ResultValue
Surface loss, % of heat input0.076993 %
Heat lost from the surface61.595 kW
Heat loss per m²153.99 W/m²
Convection coefficient5.0878 W/(m²·K)
Radiation coefficient1.0717 W/(m²·K)

Open this example in the calculator and change any input.

Formula

\(h_{cv} = 1.32\left(\frac{\Delta T}{H}\right)^{1/4} \;(H^3\Delta T \le 10) \qquad h_{cv} = 1.74\,\Delta T^{1/3} \;(\text{otherwise})\)

\(h_r = \varepsilon\,\sigma\,\frac{T_s^4 - T_a^4}{T_s - T_a} \qquad \dot Q_r = (h_{cv} + h_r)\,A\,(T_s - T_a) \qquad q = \dot Q_r/A \qquad L_r = \dot Q_r/\dot Q_{in}\)

Variables

Symbol Meaning SI unit
\(A\) outer surface area m²
\(T_s\) mean outer surface temperature K
\(T_a\) surrounding air temperature K
\(\Delta T\) surface minus air temperature K
\(\varepsilon\) surface emissivity –
\(H\) wall height m
\(\dot Q_{in}\) heat input from fuel, on the basis (GCV or NCV) of the efficiency it is compared with W
\(L_r\) surface loss, fraction of input –
\(\dot Q_r\) heat lost from the surface W
\(q\) heat loss per unit area W/m²
\(h_{cv}\) natural convection coefficient W/(m²·K)
\(h_r\) radiation coefficient W/(m²·K)
\(\sigma\) Stefan–Boltzmann constant, 5.670 374 419 × 10⁻⁸ W/(m²·K⁴)

Method and standards

Natural convection from vertical walls in still air by the ISO 12241 equations (laminar 1.32 (ΔT/H)¼, turbulent 1.74 ΔT⅓, switching at H³ΔT = 10 m³·K) and radiation to surroundings at air temperature. ASME PTC 4 §5.14 lets the surface loss be measured this way or taken from the ABMA curve; this calculator measures it.

Where it is used

  • Efficiency tests, when the surface loss is measured rather than read from a standard curve.
  • Insulation audits: finding hot spots on casings, ducts, headers and drums.
  • Shell (fire-tube) and small water-tube boilers, where surface loss is 1–3 % of input.
  • Estimating standby loss of a boiler kept hot.

Common mistakes

  • Taking one infrared reading as the mean: average many readings by area, including doors, headers and the drum.
  • Reading shiny cladding with an infrared thermometer set for emissivity 0.95: it reads far too cold.
  • Ignoring wind on outdoor boilers: forced convection can double the loss.
  • Using a full-load percentage at part load.

Assumptions and limits

  • Still air; surroundings at air temperature; all the area treated as vertical wall of one height. Roofs, horizontal ducts and pipes have other convection coefficients (ISO 12241 gives them); calculate those parts separately if they are large.
  • ASME PTC 4 measures this loss with its own coefficients and air velocity; the ISO 12241 still-air result is close but not identical.
  • One mean surface temperature and emissivity for the whole area.

References

  • ISO 12241:2008 Thermal insulation for building equipment and industrial installations (vertical walls)
  • ASME PTC 4-2013 §5.14 (surface radiation and convection loss)

Questions and answers

How do I calculate a boiler's radiation loss?

Measure the casing surface temperature, then add the natural-convection and radiation heat transfer from the surface to the room. 400 m² of aluminium cladding at 55 °C in 30 °C air loses 154 W/m², 62 kW in all, 0.08 % of an 80 MW input.

Why does emissivity matter so much?

Radiation depends on it directly. Bright aluminium (about 0.1) radiates a sixth as much as painted steel (about 0.9) at the same temperature, so the same surface reading means a very different loss.

Why is the loss larger at part load?

The casing loses about the same heat whatever the load, so as a share of a smaller input it grows. A boiler at 25 % load has about four times the percentage loss it has at full load.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators