Worked example
Example: Half load. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Efficiency at full load | 86.000 % |
| Fixed losses at full load (share of input) | 1.5000 % |
| Load (share of full-load output) | 50.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Proportional losses | 12.500 % |
| Fixed losses at this load (share of input) | 2.9494 % |
| Efficiency at this load | 84.551 % |
Open this example in the calculator and change any input.
Formula
\(L_p = 1 - \eta_{100} - L_f, \quad \dot Q_{in}(\lambda) = \frac{\lambda \eta_{100} + L_f}{1 - L_p}, \quad L_{f,\lambda} = \frac{L_f}{\dot Q_{in}(\lambda)}, \quad \eta_\lambda = \frac{\lambda \eta_{100}}{\dot Q_{in}(\lambda)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\eta_{100}\) | Efficiency at full load | - |
| \(L_f\) | Fixed losses at full load (share of input) | - |
| \(\lambda\) | Load (share of full-load output) | - |
| \(L_p\) | Proportional losses | - |
| \(L_{f,\lambda}\) | Fixed losses at this load (share of input) | - |
| \(\eta_\lambda\) | Efficiency at this load | - |
| \(\dot Q_{in}(\lambda)\) | Heat input at this load, as a share of full-load input | - |
Method and standards
Loss model (per unit of full-load input).
Where it is used
- Boiler loading decisions.
- Energy audits.
Common mistakes
- Treating all losses as fixed.
Assumptions and limits
- Proportional losses constant (as a share of input); excess air and stack temperature changes with load are ignored, so this is the minimum fall in efficiency.
- Above full load the model raises the efficiency slightly; in practice the stack temperature rises, so treat overload results with care.
References
- Loss model: proportional losses (share of input) constant; fixed losses constant in kW (ASME PTC 4 radiation and convection loss concept)
Questions and answers
Why does efficiency fall at low load?
Radiation and casing losses stay nearly constant in kW while the output falls.
Is that all?
No: excess air and stack temperature also change; use test data where you have it.
Two boilers at half load or one at full?
One at higher load is usually more efficient, if availability allows.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.