FireCADCalc

Boiler Efficiency by the Direct (Input–Output) Method

Boiler efficiency from measured steam flow, steam and feedwater conditions, blowdown, fuel flow and gross calorific value, with the evaporation ratio.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileASME PTC 4 (fired steam generators)IAPWS-IF97 (water and steam)BoilerBoiler attendant and boiler operator examinationsBoiler operation engineer (BOE) examinations

Inputs

Examples: Shell boiler 10 t/h, 10.5 bar(a) saturated, feed 105 °C, coal 1.65 t/h at 18.6 MJ/kgWater-tube 50 t/h, 66 bar(a) / 485 °C, feed 150 °C, oil 3.68 t/h at 42.5 MJ/kg, 2 % blowdownBagasse 60 t/h, 45 bar(a) / 400 °C, feed 120 °C, 28 t/h at 9.7 MJ/kg, 3 % blowdownWater-tube 50 t/h, 66 bar(a) / 485 °C, drum 72 bar(a), 2 % blowdown

For a superheated boiler the drum runs above the steam outlet pressure by the superheater pressure drop. Leave at 0 to take the steam pressure.

Results

Boiler efficiency (on GCV)60.027%
Heat to steam and blowdown45,287kW
Heat input from fuel75,444kW
Evaporation ratio2.1429kg/kg
Steam enthalpy3,205.6kJ/kg
Feedwater enthalpy506.81kJ/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Shell boiler 10 t/h, 10.5 bar(a) saturated, feed 105 °C, coal 1.65 t/h at 18.6 MJ/kg. The inputs, in the units selected above:

InputValue
Steam flow10,000 kg/h
Steam pressure (absolute)10.500 bar
Steam conditionDry saturated
Steam temperature (superheated only)250.00 °C
Feedwater temperature105.00 °C
Fuel flow1,650.0 kg/h
Gross calorific value of the fuel, as fired18,600 kJ/kg
Blowdown, as a share of steam0 %
Drum pressure (absolute), for blowdown and feedwater; 0 = steam pressure0 bar

Applying the formula below gives:

ResultValue
Boiler efficiency (on GCV)76.183 %
Heat to steam and blowdown6,494.6 kW
Heat input from fuel8,525.0 kW
Evaporation ratio6.0606 kg/kg
Steam enthalpy2,779.0 kJ/kg
Feedwater enthalpy440.90 kJ/kg

Open this example in the calculator and change any input.

Formula

\(\eta = \frac{\dot Q_{out}}{\dot Q_{in}} = \frac{\dot m_s\,(h_s - h_{fw}) + b\,\dot m_s\,(h_f - h_{fw})}{\dot m_f \cdot GCV}\)

\(\text{evaporation ratio} = \dot m_s/\dot m_f\)

Variables

Symbol Meaning SI unit
\(\dot m_s\) steam flow kg/s
\(p\) steam pressure, absolute Pa
\(\text{state}\) saturated or superheated steam –
\(T_s\) steam temperature (superheated steam) K
\(T_{fw}\) feedwater temperature K
\(\dot m_f\) fuel flow kg/s
\(GCV\) gross calorific value of the fuel, as fired J/kg
\(b\) blowdown as a share of steam flow –
\(\eta\) boiler efficiency on GCV –
\(\dot Q_{out}\) heat given to steam and blowdown W
\(\dot Q_{in}\) heat input from fuel W
\(\dot m_s/\dot m_f\) evaporation ratio, kg steam per kg fuel kg/kg
\(h_s\) steam enthalpy J/kg
\(h_{fw}\) feedwater enthalpy at the drum pressure \(p_d\) J/kg
\(h_f\) saturated water enthalpy (blowdown) at the drum pressure \(p_d\) J/kg
\(p_d\) drum pressure, absolute; 0 takes the steam pressure \(p\) Pa

Method and standards

Input–output (direct) efficiency as defined in ASME PTC 4 and in the Indian practice of IS 8753: useful heat to the working fluid divided by the chemical energy of the fuel on the gross (higher) calorific value. Steam, feedwater and blowdown enthalpies from FireCAD's IAPWS-IF97.

Where it is used

  • Daily and monthly efficiency reports of process and captive boilers from the steam and fuel meters.
  • Energy audits (Bureau of Energy Efficiency, India), as the first quick check before a full loss analysis.
  • Comparing fuels, operators or shifts by their steam-to-fuel ratio.
  • Checking a vendor's guarantee when a full PTC 4 test is not justified.

Common mistakes

  • Using a steam meter set for another pressure: an orifice meter misreads when the density changes.
  • Taking GCV on the air-dried basis while weighing the fuel as fired (or the reverse): the moisture difference shifts efficiency by several points.
  • Mixing GCV and NCV: NCV-based efficiency is 4–8 points higher for coal and about 10 points for natural gas.
  • Forgetting blowdown and soot-blowing steam when the meter is downstream of them.
  • Testing over too short a period: fuel in the hopper and furnace makes short tests unreliable; test for several hours at steady load.

Assumptions and limits

  • Steady load; the fuel and steam quantities cover the same period.
  • Gross calorific value of the fuel as fired; sensible heat in fuel and air, and auxiliary power, are not counted.
  • No heat credits; steam leaving dry (saturated) or at the given temperature (superheated). Wet steam cannot be entered; carry-over moisture would make the efficiency read high.
  • Feedwater and blowdown enthalpies are taken at the drum pressure; left at 0 it is the steam pressure. In a superheater boiler the drum runs above the outlet pressure by the superheater pressure drop: enter it for the blowdown heat to be exact.
  • The 95 % warning is a FireCAD plausibility limit for non-condensing boilers.

References

  • ASME PTC 4-2013 Fired Steam Generators (input–output method)
  • BIS IS 8753 (boiler efficiency, Indian practice)
  • IAPWS R7-97(2012) IF97

Questions and answers

How is boiler efficiency calculated by the direct method?

Divide the heat given to the steam by the heat in the fuel fired. A 10 t/h boiler making saturated steam at 10.5 bar(a) from feedwater at 105 °C adds 2338 kJ per kg; burning 1.65 t/h of coal at 18.6 MJ/kg it is 76.2 % efficient, with an evaporation ratio of 6.06.

Direct or indirect method?

The direct method needs only two meters and a fuel sample, but a 2 % error in the steam or fuel meter is a 2 % error in efficiency, and it says nothing about where the heat goes. The indirect (loss) method is more accurate and shows what to fix; use both and compare.

Should blowdown be counted?

Yes, if the steam meter reads the steam only. Blowdown leaves the drum as saturated water heated from the feedwater temperature; enter it as a share of the steam flow.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.