FireCADCalc

Membrane Rejection and Log Removal Value (LRV)

Rejection, percent removal and log removal value of a membrane or other barrier from feed and permeate concentrations of particles, pathogens or solutes.

Inputs

Examples: Cryptosporidium challenge 2e6 in, detection limit 1 outTurbidity 5 NTU to 0.05 NTU

Accepted: 1E-12 to 1E+15
Accepted: 1E-12 to 1E+15

Results

LRV equals the 'number of nines': 4-log is 99.99 % removal. With a non-detect in the permeate, using the detection limit gives the demonstrable minimum LRV.

Rejection99.000%
Log removal value2.0000
Passage0.010000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Cryptosporidium challenge 2e6 in, detection limit 1 out. The inputs, in the units selected above:

InputValue
Feed concentration (any consistent unit)2,000,000 -
Permeate concentration (same unit)1.0000 -

Applying the formula below gives:

ResultValue
Rejection100.000 %
Log removal value6.3010
Passage5.0000e-07

Open this example in the calculator and change any input.

Formula

\(R = 1 - \frac{C_p}{C_f}, \quad LRV = \log_{10}\frac{C_f}{C_p}\)

Variables

Symbol Meaning SI unit
\(C_f\) Feed concentration (any consistent unit) -
\(C_p\) Permeate concentration (same unit) -
\(R\) Rejection -
\(LRV\) Log removal value -
\(C_p/C_f\) Passage -

Method and standards

Definitions of rejection and log removal.

Where it is used

  • Membrane integrity and challenge testing.
  • Pathogen credit accounting across treatment barriers.

Common mistakes

  • Using natural logarithms.
  • Mixing units between feed and permeate.

Assumptions and limits

  • Concentrations measured on the same basis and sample timing.

Questions and answers

Why use LRV instead of percent?

Pathogen removal spans many orders of magnitude; 99.9999 % and 99.99987 % look alike but are 6.0 and 5.9 log.

Can LRVs be added?

For independent barriers in series, yes: credits from filtration and disinfection add up toward the regulatory requirement.

What do the defaults represent?

An illustrative case: Cryptosporidium challenge 2e6 in, detection limit 1 out. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 12-4, eqs. 12-3 and 12-4 and Example 12-2

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.