Worked example
Example: Pilot UF on surface water: 0.95 at 50 L/m2, 0.80 at 2000 L/m2, trigger 0.5, 80 L/(m2 h). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Specific throughput at point 1 (1 mm = 1 L/m²) | 50.000 mm |
| Normalised specific flux at point 1 | 95.000 % |
| Specific throughput at point 2 (1 mm = 1 L/m²) | 2,000.0 mm |
| Normalised specific flux at point 2 | 80.000 % |
| Normalised specific flux that triggers cleaning | 50.000 % |
| Operating flux | 80.000 L/(m²·h) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Membrane fouling index | 0.10121 1/m |
| Intercept of 1/J′ at zero throughput | 1.0476 |
| Specific throughput when the trigger is reached (1 mm = 1 L/m²) | 9,410.0 mm |
| Further throughput after point 2 (1 mm = 1 L/m²) | 7,410.0 mm |
| Time to the trigger at the operating flux | 3.8594 d |
Open this example in the calculator and change any input.
Formula
\(\frac{1}{J'_{sp}} = \frac{1}{J'_{sp,0}} + MFI\cdot V_{sp}, \quad MFI = \frac{1/J'_{sp,2} - 1/J'_{sp,1}}{V_{sp,2} - V_{sp,1}}\)
\(V_{sp,clean} = \frac{1/J'_{min} - 1/J'_{sp,0}}{MFI}, \quad t = \frac{V_{sp,clean} - V_{sp,2}}{J}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_{sp,1}\) | Specific throughput at point 1 (1 mm = 1 L/m²) | m |
| \(J'_{sp,1}\) | Normalised specific flux at point 1 | - |
| \(V_{sp,2}\) | Specific throughput at point 2 (1 mm = 1 L/m²) | m |
| \(J'_{sp,2}\) | Normalised specific flux at point 2 | - |
| \(J'_{min}\) | Normalised specific flux that triggers cleaning | - |
| \(J\) | Operating flux | m/s |
| \(MFI\) | Membrane fouling index | 1/m |
| \(1/J'_{sp,0}\) | Intercept of 1/J′ at zero throughput | - |
| \(V_{sp,clean}\) | Specific throughput when the trigger is reached (1 mm = 1 L/m²) | m |
| \(\Delta V_{sp}\) | Further throughput after point 2 (1 mm = 1 L/m²) | m |
| \(t\) | Time to the trigger at the operating flux | s |
Method and standards
Resistance-in-series fouling model linear in specific throughput.
Where it is used
- Comparing fouling of source waters and membranes.
- Estimating clean-in-place intervals from pilot data.
Common mistakes
- Using raw flux without temperature and pressure correction.
- Mixing within-run and run-to-run points.
Assumptions and limits
- Fouling resistance proportional to throughput.
Questions and answers
Why use specific throughput rather than time?
Throughput per unit area lets runs of different length, flux and scale be compared; fouling builds with the volume filtered.
What do the defaults represent?
An illustrative case: Pilot UF on surface water: 0.95 at 50 L/m2, 0.80 at 2000 L/m2, trigger 0.5, 80 L/(m2 h). Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 12-7, eqs. 12-21 to 12-25 and Example 12-6 (Huang et al. 2008)