Worked example
Example: pH 6.5 groundwater, 3 to 0.1 mg/L, 2,000 m3/d. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Initial ferrous iron | 3.0000 mg/L |
| Target ferrous iron | 0.10000 mg/L |
| pH | 6.5000 - |
| Oxygen partial pressure (air 0.21 atm) | 0.21000 - |
| Rate constant (Stumm and Lee: 8 × 10¹³ L²/(mol²·atm·min) at 20 °C) | 8.0000e+13 - |
| Flow | 2,000.0 m³/d |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pseudo-first-order rate constant | 0.016800 1/min |
| Completely mixed reactor detention | 1,726.2 min |
| Completely mixed reactor volume | 2,397.5 m³ |
| Plug-flow reactor detention | 202.45 min |
| Plug-flow reactor volume | 281.18 m³ |
| Half-life of Fe²⁺ | 41.259 min |
Open this example in the calculator and change any input.
Formula
\(-\frac{d[\text{Fe}^{2+}]}{dt} = k[\text{OH}^-]^2P_{O_2}[\text{Fe}^{2+}] = k_r[\text{Fe}^{2+}]\)
\(\tau_{CMFR} = \frac{C_0 - C_e}{k_rC_e}, \quad \tau_{PFR} = \frac{1}{k_r}\ln\frac{C_0}{C_e}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_0\) | Initial ferrous iron | kg/m³ |
| \(C_e\) | Target ferrous iron | kg/m³ |
| \(pH\) | pH | - |
| \(P_{O_2}\) | Oxygen partial pressure (air 0.21 atm) | - |
| \(k\) | Rate constant (Stumm and Lee: 8 × 10¹³ L²/(mol²·atm·min) at 20 °C) | - |
| \(Q\) | Flow | m³/s |
| \(k_r\) | Pseudo-first-order rate constant | 1/s |
| \(\tau_{CMFR}\) | Completely mixed reactor detention | s |
| \(V_{CMFR}\) | Completely mixed reactor volume | m³ |
| \(\tau_{PFR}\) | Plug-flow reactor detention | s |
| \(V_{PFR}\) | Plug-flow reactor volume | m³ |
| \(t_{1/2}\) | Half-life of Fe²⁺ | s |
Method and standards
Stumm–Lee oxygenation kinetics with ideal reactor models.
Where it is used
- Sizing aeration and detention tanks for groundwater iron removal.
- Choosing pH adjustment before filters.
Common mistakes
- Using the rate constant at 20 °C for cold groundwater without testing.
- Forgetting that organic-bound iron does not follow this law.
Assumptions and limits
- pH above 5.5, no complexing organics, oxygen in excess.
Questions and answers
Why does pH matter so much?
The rate is second order in hydroxide: from pH 6.5 to 7.5 it rises 100 times.
Why is the plug-flow reactor so much smaller?
A completely mixed tank runs at the low outlet concentration, so its first-order rate is slowest; plug flow uses the full concentration range.
What do the defaults represent?
An illustrative case: pH 6.5 groundwater, 3 to 0.1 mg/L, 2,000 m3/d. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Crittenden et al., MWH's Water Treatment: Principles and Design, 3rd ed. (Wiley, 2012), sec. 20-3, eq. 20-5 (Stumm and Lee, 1961) and Example 20-2