Worked example
Example: 300 kg/h at 20 bar. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated flow | 300.00 kg/h |
| Rated pressure drop | 20.000 bar |
| Minimum pressure drop | 7.0000 bar |
| Maximum pressure drop | 25.000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow at minimum pressure | 177.48 kg/h |
| Flow at maximum pressure | 335.41 kg/h |
| Turndown ratio | 1.8898 |
Open this example in the calculator and change any input.
Formula
\(\dot m = \dot m_1\sqrt{\Delta p/\Delta p_1}, \quad TD = \sqrt{\Delta p_{max}/\Delta p_{min}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_1\) | Rated flow | kg/s |
| \(\Delta p_1\) | Rated pressure drop | Pa |
| \(\Delta p_{min}\) | Minimum pressure drop | Pa |
| \(\Delta p_{max}\) | Maximum pressure drop | Pa |
| \(\dot m_{min}\) | Flow at minimum pressure | kg/s |
| \(\dot m_{max}\) | Flow at maximum pressure | kg/s |
| \(TD\) | Turndown ratio | - |
Method and standards
Square-root law of an orifice with a constant discharge coefficient, scaled from the nozzle's rated flow and pressure. A note appears when the turndown is above about 2:1.
Where it is used
- Burner selection.
- Load range checks.
Common mistakes
- Supply pressure used instead of nozzle drop.
Assumptions and limits
- Constant viscosity and discharge coefficient. The flow number of swirl pressure-jet nozzles changes somewhat with pressure and viscosity; use the maker's capacity table where you have it.
- The minimum pressure for good atomisation is not checked: take it from the nozzle maker.
References
- Orifice square-root law ṁ ∝ √Δp (constant discharge coefficient)
Questions and answers
Why only √ of the pressure?
Flow through an orifice rises with the square root of the pressure drop.
Why is turndown small?
Doubling the flow needs four times the pressure.
Viscosity?
Heat the oil to the viscosity the nozzle needs; flow at a pressure depends on it.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.