Gas Burner Flow (Nm³/h, Actual m³/h, Velocity)

Fuel gas flow for a burner in Nm³/h and actual m³/h at line pressure and temperature, and the velocity in the gas train pipe, from heat input and net calorific value.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalPulp and paperBoilerFuel oil and gas systemBurner and furnace

Inputs

Examples: 5 MW burner, NG 34 MJ/Nm³, 2 bar(a), 20 °C, 80 mm20 MW, 35 MJ/Nm³, 5 bar(a), 25 °C, 100 mm500 kW, 34 MJ/Nm³, 1.05 bar(a), 15 °C, 50 mm

Shown as gauge (bar g, kg/cm² g, psig) as line gauges read; choose an absolute unit to enter absolute pressure.

Results

Gas flow at normal conditions (0 °C, 1.01325 bar)52.941Nm³/h
Actual gas flow in the line53.894m³/h
Velocity in the pipe7.6244m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 MW burner, NG 34 MJ/Nm³, 2 bar(a), 20 °C, 80 mm. The inputs, in the units selected above:

InputValue
Burner heat input (on NCV)5,000.0 kW
Net calorific value of the gas, per Nm³34.000 MJ/Nm³
Gas pressure in the line0.98675 bar g
Gas temperature20.000 °C
Pipe inside diameter80.000 mm
Compressibility factor1.0000 -

Applying the formula below gives:

ResultValue
Gas flow at normal conditions (0 °C, 1.01325 bar)529.41 Nm³/h
Actual gas flow in the line287.85 m³/h
Velocity in the pipe15.907 m/s

Open this example in the calculator and change any input.

Formula

\(\dot V_n = \frac{\dot Q}{NCV} \qquad \dot V = \dot V_n\,\frac{p_n}{p}\,\frac{T}{T_n}\,Z \qquad v = \frac{\dot V}{\pi D^2/4}\)

Variables

Symbol Meaning SI unit
\(\dot Q\) burner heat input on NCV W
\(NCV\) net calorific value per Nm³ J/m³
\(p\) line pressure (absolute in SI; shown and entered as gauge) Pa
\(T\) gas temperature K
\(D\) pipe inside diameter m
\(Z\) compressibility factor –
\(\dot V_n\) flow at normal conditions Nm³/s
\(\dot V\) actual flow m³/s
\(v\) velocity in the pipe m/s
\(p_n\), \(T_n\) normal pressure and temperature, 101 325 Pa and 273.15 K Pa, K

Method and standards

Ideal-gas conversion between normal and line conditions with a compressibility factor.

Where it is used

  • Sizing gas trains, regulators and meters.
  • Checking burner gas consumption against the meter.
  • Gas supply contracts and budgets.

Common mistakes

  • Using GCV with an efficiency on NCV, or the reverse.
  • Treating gauge pressure as absolute.
  • Mixing normal and standard cubic metres.

Assumptions and limits

  • Single gas composition; compressibility at line conditions as entered (1 is fine at low pressure); at normal conditions Z is taken as 1 (about 0.998 for natural gas, a 0.2 % difference).
  • Normal volumes are at 0 °C and 101.325 kPa, and the NCV per Nm³ is on that same basis; scfm and Btu/scf are converted to the US standard cubic foot (60 °F, 14.696 psia).
  • The 20 m/s velocity warning is a common design limit, not a code value.

References

  • Ideal-gas law with compressibility; normal conditions 0 °C and 101.325 kPa

Questions and answers

How much gas does a 5 MW burner use?

Heat input over NCV: 5 MW at 34 MJ/Nm³ is 529 Nm³/h. At 2 bar(a) and 20 °C that is 288 m³/h actual, 15.9 m/s in an 80 mm pipe.

Why convert to actual m³/h?

Pipes, valves and meters see the actual volume at line pressure. Sizing on Nm³/h overstates the volume of pressurised gas.

Normal or standard cubic metres?

Normal is 0 °C and 101.325 kPa; "standard" conditions vary (15 °C or 20 °C). Check which one your gas bill and calorific value use.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.