Fuel Saving from Reducing Excess Air (O₂)

Efficiency gain and fuel saved by lowering the flue gas O₂ (excess air), from the fuel analysis, the gas and air temperatures and the present efficiency.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalPulp and paperASME PTC 4 (fired steam generators)BoilerBurner and furnaceFan and blower

Inputs

Examples: Indian coal, O2 6 % to 4 %, gas 160 °CNatural gas (methane), O2 5 % to 2.5 %, gas 180 °CFuel oil, O2 4.5 % to 3 %, gas 200 °C

Keep it where CO stays low; the burner maker or a combustion test sets the floor.

Ultimate analysis, as fired, by mass

Results

Fuel saved, share of present fuel0.93392%
Fuel saved112.07kg/h
Efficiency after76.716%
Excess air now38.863%
Excess air after22.852%
Sensible flue gas loss now6.8861%
Sensible flue gas loss after6.1696%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Indian coal, O2 6 % to 4 %, gas 160 °C. The inputs, in the units selected above:

InputValue
O₂ in dry flue gas now6.0000 %
O₂ in dry flue gas after tuning4.0000 %
Carbon45.000 %
Hydrogen3.5000 %
Oxygen5.0000 %
Nitrogen1.0000 %
Sulphur0.50000 %
Ash35.000 %
Moisture10.000 %
Air humidity (kg water per kg dry air)0.013000 kg/kg
Gross calorific value of the fuel, as fired18,600 kJ/kg
Flue gas temperature at the boiler exit160.00 °C
Combustion air temperature30.000 °C
Boiler efficiency now (on GCV)76.000 %
Fuel firing rate12,000 kg/h

Applying the formula below gives:

ResultValue
Fuel saved, share of present fuel0.93392 %
Fuel saved112.07 kg/h
Efficiency after76.716 %
Excess air now38.863 %
Excess air after22.852 %
Sensible flue gas loss now6.8861 %
Sensible flue gas loss after6.1696 %

Open this example in the calculator and change any input.

Formula

\(n_{a,0} = \frac{1}{0.2095}\left(\frac{C}{12.011} + \frac{H}{4.032} + \frac{S}{32.06} - \frac{O}{31.998}\right), \quad n_{dg,0} = \frac{C}{12.011} + \frac{S}{32.06} + \frac{N}{28.014} + 0.7905\,n_{a,0}\)

\(EA = \frac{O_2\,n_{dg,0}}{n_{a,0}\,(0.2095 - O_2)} \qquad L = \frac{m_g(EA)\,\left[h_g(T_g) - h_g(T_a)\right]}{GCV}\)

\(\eta_2 = \eta_1 + L_1 - L_2 \qquad s = 1 - \frac{\eta_1}{\eta_2} \qquad \Delta\dot m_f = s\,\dot m_f\)

Variables

Symbol Meaning SI unit
\(O_{2,1}\) O₂ in dry flue gas now –
\(O_{2,2}\) O₂ in dry flue gas after tuning –
\(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) ultimate analysis as fired, mass fractions –
\(\omega\) air humidity, kg water per kg dry air kg/kg
\(GCV\) gross calorific value J/kg
\(T_g\) flue gas temperature at the boiler exit K
\(T_a\) combustion air temperature K
\(\eta_1\) boiler efficiency now, on GCV –
\(\dot m_f\) fuel firing rate now kg/s
\(s\) fuel saved, share of present fuel –
\(\Delta\dot m_f\) fuel saved kg/s
\(\eta_2\) efficiency after –
\(EA_1\) excess air now –
\(EA_2\) excess air after –
\(L_1\) stack loss now –
\(L_2\) stack loss after –
\(EA\), \(O_2\) excess air and dry O₂ in general –
\(n_{a,0}\) theoretical dry air per kg fuel kmol/kg
\(n_{dg,0}\) dry flue gas per kg fuel at zero excess air kmol/kg
\(m_g\) wet flue gas per kg fuel kg/kg
\(h_g\) enthalpy of the wet flue gas J/kg

Method and standards

Excess air from the dry O₂ by an exact oxygen balance of the fuel analysis. Stack loss (dry gas plus water vapour sensible heat between the air and gas temperatures) from FireCAD's combustion balance and NIST Shomate enthalpies, as in the ASME PTC 4 losses. The CO loss is not included: keep O₂ above the point where CO rises.

Where it is used

  • Combustion tuning and O₂ trim projects on boilers, furnaces and thermic fluid heaters.
  • Energy audits: valuing an O₂ analyser or a trim system.
  • Explaining to operators why "more air for safety" costs fuel.

Common mistakes

  • Reading O₂ after an air heater or a leaking duct, which shows more excess air than the furnace has.
  • Going below the CO floor: the CO loss and soot rise faster than the dry gas loss falls.
  • Assuming the exit gas temperature stays the same; it usually falls slightly with less excess air, adding a little to the saving.

Assumptions and limits

  • Exit gas and air temperatures unchanged; complete combustion at both O₂ levels.
  • Water vapour leaves as vapour (no condensation).
  • Dry-basis analyser and complete combustion: CO, unburned carbon and air in-leakage are not modelled. The fuel enters at the air temperature (no separate fuel sensible heat).
  • If the O₂ after is higher than now, the result is an extra fuel use (negative saving), with a note.
  • The flue gas losses shown are sensible heat only. The latent heat of the water from hydrogen and moisture does not change with excess air, so it cancels in the saving but is not part of the loss figures.

References

  • ASME PTC 4-2013 §5.14 (dry gas and water vapour losses)
  • NIST Chemistry WebBook Shomate equations

Questions and answers

How much fuel does lowering O₂ save?

For coal with gas leaving at 160 °C, cutting O₂ from 6 to 4 % (excess air 39 to 23 %) lowers the sensible stack loss from 6.89 to 6.17 % (the latent heat of the water is not counted; it does not change) and saves 0.93 % of the fuel. The saving grows with the gas temperature.

How low can O₂ go?

Until CO starts to rise. Gas burners often run at 1.5–3 % O₂, oil at 2–4 %, pulverised coal at 3–4 %, grate and biomass at 5–8 %. Find the floor with a combustion test and keep a margin.

Does lower excess air save fan power too?

Yes. Less air and less flue gas mean less FD and ID fan power, often a further 5–15 % of fan power on top of the fuel saving.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.